SECTION 5 – INSTALLATION INSTRUCTIONS
UL EX3470 ULC EX3470
2014-SEP-01 REV. 11 PAGE 5-29
R-102 Restaurant Fire Suppression Manual
INSTALLATION OF REMOTE MANUAL PULL STATION OR
MECHANICAL GAS VALVE UTILIZING FLEXIBLE CONDUIT
(Continued)
Connecting the Block and the Faceplate (Continued)
9. Snap the pull tab onto the pull knob so it is legible. See
Figure 5-85.
FIGURE 5-85
008018
10. Refer to R-102 or PIRANHA installation manual to complete
system installation.
11. Test Remote Manual Pull Station and Mechanical Gas
Valves in accordance with the “Testing and Placing
in Service – Testing Manual Pull Station and Testing
Mechanical Gas Valves” section of this manual.
Installing Flexible Conduit Through a Conduit Offset
1. Starting at the AUTOMAN release, connect the conduit
connector using the supplied nut. Use only ANSUL conduit
fittings (Part No. 55813). See Figure 5-86.
FIGURE 5-86
007986
2. Install Conduit Offset (Part No. 435961) into conduit
connector and tighten nut. See Figure 5-87.
FIGURE 5-87
008039
3. Install compression union to opposite end of conduit offset.
Tighten securely. See Figure 5-88.
FIGURE 5-88
008040