Maintenance
81
MAXXflo EVO
Error
Code
Error Code Description
Diag.
Code
Notes
130
Flue gas temperature too high
Any
Check causes of high temperatures before operating Appliance.
Inspect inside of heat exchanger for dirt build up. Check CO
2
levels at min and max output.
133
Safety time exceeded
395
Records individual ignition failures and the times they have
occurred. Check gas supply, spark electrode, spark generator,
Ionisation probe, CO
2
setting and flue system
625
A total of 5 unsuccessful ignition attempts has occurred within a
24 hour period. This is the point that the heater went into perme
-
nant lockout
142
Device failure (Bus)
Any
Check that the appliance and OZW672 is powered and con
-
nected correctly.
151
BMU Internal error
330
331
Ignition output error. Check operation of spark generator. Re
-
place PCB if no fault with the spark generator found.
332
333
Gas valve output error. Check operation of gas valve. Replace
PCB if no fault with the gas valve found.
Other
Check if polarity of live and neutral has been reversed to the ap
-
pliance. Replace PCB if fault repeatedly occurs.
152
Parameterization error
Any
Incorrect / conflicting parameters input (last changed param
-
eters need to be investigated).
153
Unit Locked
622
Temperature inside the appliance casing has exceeded 90
O
C.
Check heat engine door seals and door nuts are correctly
tightened. Pressing the reset for more than 10 seconds will also
produce this lockout.
848
849
Parameter update finished. Press reset to apply changes.
160
Fan speed threshold not
reached
Any
Fan does not reach required speed setpoint via PWM control-
Check wiring and operation of fan. Replace fan if necessary
377
Fan speed not reached - Home run stage
378
Fan speed not reached - Standby stage
379
Fan speed not reached - Ignition stage
380
Fan speed not reached - Pre purge stage
381
Fan speed not reached - Post purge stage
162
Air pressure switch
Any
Air pressure switch has activated or is open circuit. Check for
flue restriction or incorrect flue installation. Check air pressure
switch function (operates at 365 Pa). Condense pipework may
be blocked. Check the condensate pipe system is free to flow
into the trap and beyond.
171
Fault input 1
Any
User defined OZW672 input D1 has been activated.
172
Fault input 2
Any
User defined OZW672 input D2 has been activated.
183
Unit in parameterisation mode
Any
Code will be displayed when a programming stick is used but
should clear when programming is complete. Repeat stick op
-
eration if fault code persists
217
Sensor error
Any
Ionisation current fault or short circuit. Check operation of ioni
-
sation probe using parameter 8329 (menu - Diagnostics heat
generation). Ionisation probe may need replacing. Check earth
-
ing to the heater
218
Pressure supervision
Any
Water pressure inside appliance is low but not yet critical. Ap
-
pliance will continue to operate but at 80% of maximum output.
Full output power will not be available until the water pressure is
at or above 0.2 bar.
6.6 ERROR CODES (CONTINuED)