Maintenance
65
MAXXflo EVO
CAuTION
Changing the following components will require some draining of the water system. It is essential
that all the air is removed from the heat exchanger before the heater is operated. To not do so may
damage the heat exchanger and invalidate the warranty.
6.2.13 HEAT EXCHANGER
• Turn off the water isolators located before and after the heat exchanger (see below):
• Drain water using the drain points to ensure the heat exchanger is as empty as possible.
• Disconnect all electrical connections to the flue, flow and return sensors.
• Disconnect the flue from the top of the heat exchanger by pushing the flue section upwards so that it
clears the heat exchanger
• Disconnect the electrical connections to the ionisation probe, ignition probe, fan and gas valve and place
wiring to one side.
• Remove the air intake from the venturi by squeezing the spring clip together, and disconnect offset tube
Push assembly
upwards
Flue sensor connector
Return sensor connector
Flow sensor connector
Gas valve
connectors
Fan connectors
Spring clip
Ionisation probe
Ignition probe
Isolation valve
Isolation valve
Isolation valve