A Secondary Return circuit may be fitted to the 1” nipple at the top of the heater. In all cases, for serviceability,
the recirculation pipe must be fitted with a stop valve immediately before the connection point.
See Section 3.6 Example 1 for wiring details
If a secondary return circuit is fitted with a secondary pump, please ensure that the flow-rate does not exceed
the heater maximum flow-rate, An excessive flow in the secondary circuit could result in a temperature mixing
effect in the heater storage vessel, resulting in a stored water temperature less than set temperature.
See table below:-
It is important that the heat losses from the return system are minimised (through pipe
insulation), otherwise the heater may be operating for extended periods of time on minimum
load, constantly replacing the heat lost from the return system pipes.
4.5 SECONDARy RETuRN DESIGN (DHw CIRCuLATION PuMP)
Model Type
MAXXflo
EVO 90
MAXXflo
EVO 120
Maximum flow rate m
3
/h
1.8
2.4