Page 25
ZONESENSE DH4
OPERATORS MANUAL
7.4.1 Example of Disabling the Fault Output
Step 1:
Enter the level 2 password by pressing these
keys in the following order.
The
LED will illuminate (steady)
Step 2:
Press
and the Zone 1 FAULT/DISABLE/TEST LED will flash and
will
flash. (slow for enabled, fast for disabled).
Step 3:
Press
to step through the options until
LED is illuminated
(slow for enabled, fast for disabled)) and press
again. The Fault Output Disabled LED
will continue flashing while the disablement is being established and then become steady once the
disablement is established as will the
LED.
Note:
Disablement and re-enablement of any of the above is not affected by Reset from the fire
alarm condition or the fault condition and can only be carried out by following the appropriate
procedure at access level 2.
Note:
Disable has priority over the fault condition. Disabling a zone will override the alarm
condition and cause any outputs activated as a result of the zone going into alarm to be cleared.