Page 18
ZONESENSE DH4
OPERATORS MANUAL
Operation of the silence/resound control has no effect on the door holder
output state
Activating the reset switch, will cancel the evacuate condition, which results in the alarm outputs
being turned off, door holder outputs activated and the common fire led being extinguished.
Next
- Active at access level 1 and 2.
At access level 1, the Next
key is used to enter the 0 digit of the 3210 password.
At access level 2, the Next
key is used to select zone circuits for the walk test and outputs for
disable / re-enable.
Lamp Test
- Active at access level 1 and 2.
At access level 1, the Lamp Test
key is used to enter the 1 digit of the 3210 password, and
instigate a lamp and buzzer test if the key is depressed for 3 seconds or more. The lamp test
sequentially illuminates all indicators and sounds the buzzer for approximately 1 second.
Note:
The lamp test will be cancelled if a fire condition is to be announced and can not be
instigated if a fire condition is present.
Note:
The lamp test is cancelled if a fault condition is to be announced but can be instigated if a
fault condition is present.
At access level 2, the Lamp Test
key is used to commence the walk test.
Disable/Enable
Active at access level 1 and 2
At access level 1, is used to enter the 2 digit of the 3210 password.
At access level 2, is used to disable / enable selected zones and / or outputs.
Exit
Active at access level 1 and 2.
At access level 1, Exit
is used to enter the 3 digit of the 3210 password.
At access level 2, Exit
is used to exit from the disable / enable, and walk test procedure.