Page 20
ZONESENSE DH4
OPERATORS MANUAL
Test - Amber
Illuminated to show that the FACP is in the Walk Test mode. The indicator is illuminated steady
when the walk test is active.
Fire Output On - Red
Illuminates steady when the “Fire Output” relay is active as a result of a fire condition.
6.3.2 Control
Indicators
There are five (5) control indicators within the central control area of the FACP.
Common Fire - Red
Common fire indicator will be flashing at the alarm rate when a fire condition is present or the
evacuate control is operated (when the FACP is at access level 2). The indicator will become steady
when silence resound switch is pressed.
A new fire condition or activation of the evacuate control will cause the indicator to flash again.
Common Fault - Amber
Fault indicator - illuminated steady by any fault condition.
Disabled - Amber
Disabled indicator illuminated steady by any disablement on any zone or output.
Door Released - Amber
The indicator is illuminated when the door holder outputs (1 & 2) have been deactivated.
Alarms Status - Amber
This indicator is immediately above the Alarms silence / resound switch and indicates a disable
condition (steady) or a fault condition (flashing at the fault rate) on any of the alarm outputs.
Display priority: Disable (steady) then fault (flash)