Page 17
ZONESENSE DH4
OPERATORS MANUAL
Level 3
Used to Enable / Disable Battery Monitoring
Enter the level 2 password as shown above.
Press the ANC PROG button (SW11). The panel should beep.
Switch 1 of SW10 can now be toggled to Disable / Enable battery monitoring. (Switch 1 ‘ON’
battery monitoring enabled. Switch 1 ‘OFF’ battery monitoring Disabled (See Figure 7)
Press the Exit key to return to level 1
Battery Monitoring can be verified by entering level 3 again. The POWER FAULT indicator
should be steady for Enabled battery monitoring or Off if Disabled.
Door Release - Active at access level 2 and above
Control is used to de-activate the door holder outputs (1 and 2) which release the doors. Door holder
outputs remain de-activated until cleared by the reset control.
Silence / Resound Alarms - Active at access level 2
Used to turn off the alarm outputs once they have been operated by a fire or evacuate condition.
In the event of a new fire condition the alarm outputs will again operate. Pressing a second time
reactivates the Alarm outputs once they have been silenced.
Silencing an alarm will cause the Common Fire LED and any Zone Fire LED to change from flashing
to steady.
Silence Buzzer - Active at access level 1 or above
Used for silencing either the fault or alarm warning buzzer at access level 1 and above. The buzzer
will resound on any new event.
Reset - Active at access level 2
The reset control is used to return the FACP back to a quiescent state from a fire alarm or fault
condition and to extinguish the “System Fault Indicator”. This means all zone circuits are reset for 2
seconds.
As a result of the reset, all alarm outputs, and fire output will be switched off, and the door holder
outputs activated
Where a fault condition is cleared as a result of a reset, and if the fault condition is still prevailing, it
shall be appropriately reflected at the FACP within 20 seconds. The fault conditions that are cleared
by Reset are system fault and any zone related faults. All other faults are non latching
The reset button is unique and is not to be used for any other purpose.
Note:
Reset is also used to extinguish the System Fault indicator.
Evacuate - Active at access level 2
Turns on and latches alarm outputs and local buzzer and the common Fire indicator flashing. The
door holder outputs are switched off. No other outputs or indicators are affected.
Activating the silence / resound alarms control, will turn off the alarm outputs, and cause the
common fire LED to go steady. Activating the silence / resound again will cause the alarm outputs to
be activated and common fire LED to flash.