ZONESENSE DH4
OPERATORS MANUAL
7
FACP
Operation
7.1 Normal
Condition
The FACP is in its normal condition when there are no;
Fire
alarm/s
Fault/s
Disable/s
Testing
Programming
The power indicator is illuminated steady ( indicating mains power is available ) and
The door holder outputs shall be activated.
The FACP can be in access level 1 or access level 2. If the FACP is at access level 2, then the
Controls Enabled LED will be illuminated steady.
7.2
Fire Alarm Condition
General Conditions
An alarm is triggered when any of the detectors on a zone circuit sense a fire or a manual
call point is manually operated.
Each zone operates in isolation to the others.
If a zone/s circuit/s have been disabled the FACP is prevented from initiating an alarm
condition on that zone circuit.
If a lamp test is in progress when an incoming alarm is recognised it will be aborted.
If the FACP is in programming mode when an alarm is recognised, then programming mode
is aborted.
When the FACP is in the fire alarm condition, then the fire output will be activated immediately
Associated with the fire output is the fire output on indicator.
The fire output can be disabled (isolated). If the fire output is disabled, then it is not activated as
detailed above, and the fire output disabled indicator is illuminated.
The door holder outputs are de-activated immediately.
Indication of the Fire Alarm Condition
The fire alarm indications are the;
Common fire indicator flashes (goes steady when the Silence Resound button is pressed)
Individual zone fire indicator flashes (goes steady when the Silence Resound button is
pressed)
Buzzer sounds. Press the silence buzzer control (reminder; the buzzer will resound for each
new zone that goes into alarm)
Alarm sounders and enabled outputs will be activated.
Subsequent Alarms
If at any time after the first alarm occurs other alarms are initiated the FACP will;
Reactivate the buzzer, alarm sounders and outputs if they have been silenced
Flash the Common Fire indicator
Flash the appropriate zone Fire indicator of the zone that has come into alarm
Continue to indicate ( flashing ) the previous zone or zones that were in the alarm condition (
steady when the Silence button was pressed)