![amiad TEQUATIC PLUS F-150 C Series Скачать руководство пользователя страница 33](http://html.mh-extra.com/html/amiad/tequatic-plus-f-150-c-series/tequatic-plus-f-150-c-series_installation-operation-and-maintenance-manual_2932279033.webp)
Amiad Water Systems | 2019
TEQUATIC™ PLUS F-150 Filter, C-series Skid
33
Operation
Alarm Descriptions
ID
Name
Alarm text [en-US], Alarm text
Trigger Tag
Bit
1
Discrete_alarm_1
Emergency Stop
Alarm_Word1
8
2
Discrete_alarm_3
High Differential Pressure (1st)
Alarm_Word1
9
3
Discrete_alarm_4
Low Brush Speed
Alarm_Word1
10
4
Discrete_alarm_5
High DP/Low Brush Attempts
exceeded
Alarm_Word1
11
5
Discrete_alarm_6
DP Event Maximum exceeded
Alarm_Word1
12
6
Discrete_alarm_7
Low Feed Pressure
Alarm_Word1
13
7
Discrete_alarm_8
High Feed Pressure
Alarm_Word1
14
8
Discrete_alarm_9
Feed Tank Low
Alarm_Word1
15
9
Discrete_alarm_2
Feed Pump Fault
Alarm_Word1
0
10
Discrete_alarm_11
Recirculation Pump Fault
Alarm_Word1
1
11
Discrete_alarm_12
Purge Valve 1 Fault
Alarm_Word1
2
12
Discrete_alarm_13
Purge Valve 2 Fault
Alarm_Word1
3
13
Discrete_alarm_14
Purge Valve 3 Fault
Alarm_Word1
4
14
Discrete_alarm_15
Air Bleed Valve Fault
Alarm_Word1
5
15
Discrete_alarm_16
Filtrate Valve Fault
Alarm_Word1
6
16
Discrete_alarm_17
Filtrate Tank High
Alarm_Word1
7
17
Discrete_alarm_10
High Differential Pressure (2nd)
Alarm_Word2
8
18
Discrete_alarm_18
High Differential Pressure (3nd)
Alarm_Word2
9
19
Discrete_alarm_19
Max CIP Event/Period Reached
Alarm_Word2
10
Hard Outputs
Address
Symbol
Description
Signal
Note
Q0.0
SQ1
Spare Relay
24 VAC
Relay
Q0.1
OPEN
Open Relay
24 VAC
Relay
Q0.2
SQ2
Spare Relay
24 VAC
Relay
Q0.3
FE
Feed Pump Enable Relay
24 VAC
Relay
Q0.4
EXA
External Alarm
24 VAC
Relay
Q0.5
AV
Air Valve
24 VAC
External Encl.
Q0.6
HV
Clean In Place Hot Valve
24 VAC
External Encl.
Q0.7
IV
Feed Inlet Valve Relay
24 VAC
External Encl.
Q1.0
CP
Clean In Place Chemical Pump
24 VAC
External Encl.
Q1.1
OPEN
Spare Valve
24 VAC
External Encl.