TEQUATIC™ PLUS F-150 Filter, C-series Skid
22
Controls Overview
3.2.7 Clean In Place, CIP
This screen allows all settings for the CIP event to be
set. This function requires an add-on kit that includes
additional valves, plumbing, and wiring. With the
components installed the proper function can be utilized.
•
Chem Duration, Dwell Duration, Pause Duration, and
Filtrate Bump will adjust the timing of the action taken
during the CIP event. The valve action diagram shown
below describes the interactions of these settings.
•
Schedule: When enabled, this will trigger a CIP event
based on the Frequency timer.
•
Cycles: This determines the number of CIP cycles that occur during a single CIP event.
•
Shutdown CIP: Enabling this will trigger a CIP event whenever the system is shut down at the HMI
screen. It is not recommended to be used in conjunction with a tank level switch and automatic
restart.
•
DP Event CIP: This will trigger a CIP event instead of a forward spin in the case of high differential
pressure event.
•
Max CIP Events/Period: If the maximum CIP Events per time frame is exceeded the system will not
perform the CIP but will continue running. This is intended to limit chemical usage and system
downtime.
CIP Valve Action Diagram