Amiad Water Systems | 2019
TEQUATIC™ PLUS F-150 Filter, C-series Skid
12
Installation
2.3.3 Plumbing
Plumbing into the TEQUATIC™ PLUS
Filter skid system uses 1, 2, and 2.5
inch class 150 ANSI flanges that will
allow the installation of fittings to
adapt into the facility plumbing. The
actual plumbing layout will depend on
the complete system design.
2.4 Electrical
The system requires a 3-phase, grounded supply
circuit.
Make sure the circuit is installed in accordance
with all applicable electrical codes.
The main disconnect lugs are rated for stranded
copper, up to 3/0 maximum conductor size. All
conductors must be rated for 75
°
C.
Note:
The actual enclosure layout may
vary slightly depending on system voltage
considerations.
FILTRATE 2.5"
FLANGE
CLASS 150
HOT WATER (CIP)
1.0" FLANGE
CLASS 150
FEED
2.5" FLANGE
CLASS 150
DRAIN 1.0"
FLANGE
CLASS 150
PURGE
2" FLANGE
CLASS 150
L1
L2
L3
Ground
Electrical
Disconnect