Controls Overview
3.2.1 Pump Settings
The pump settings can be adjusted in this screen. The
recirculation pump is standard to the C-Series skid and
should always be enabled. The system will send a run
command to an external feed pump by enabling the
feed pump. The fault delay is the time allowed between
sending a run command and receiving feedback before
a fault is triggered. Start and stop delays are intended
for custom applications and should remain set to zero.
The speed of the recirculation pump can be set here as a
percent of the maximum available speed for the pump.
3.2.2 Valve Settings
This screen sets the basic parameters for any installed
valves. Touch the valve name to select which of the
installed valves to view the settings for. This will be
Filtrate Valve (Manual, DP, or Flow) and Purge Valve.
•
Enable/Disable: Sets whether the valve is available to
the system or not.
•
Feedback: Sets whether the valve is capable of feedback
(open/closed/position) and whether this feedback is
available to the system.
•
Fault Delay: Once a valve has been signaled to close,
the PLC will look for feedback to confirm complete
cycling of the valve. If feedback is not received once the
delay timer has expired a fault will be triggered.
•
Schedule: Sets whether the valve should function on a
timed schedule.
•
Frequency: Sets how often (in minutes) the valve
should be operated when Schedule is enabled.
•
Duration: Sets how long (in seconds) the valve
should be operated when Schedule is enabled.