Amiad Water Systems | 2019
TEQUATIC™ PLUS F-150 Filter, C-series Skid
32
Operation
4.5 SCADA Integration
Networking is performed using the Scalance communication switch and two types of communication
are supported, Profinet and Siemens Industrial Ethernet. To communicate to a non-native SCADA
a gateway is needed to translate the messages. Each skid must be treated as a slave unit accepting
commands from the SCADA and allowing sampling of the software variables.
The network integration is intended to only allow start and stop control of the system while
monitoring important variables and alarms. A start or stop command must be a momentary signal, on
for a short time and then back off. If the signal is continuous the system will not run properly. Below
are the tags provided in a non-optimized data block.
Virtual Tags
Variable
Data
Format
Address
Comments
Start_Command
Bool
db99.dbx0.0
Momentary
Stop_Command
Bool
db99.dbx0.1
Momentary
Skid_off
Bool
db99.dbx2.0
Skid_off_waiting
Bool
db99.dbx2.1
Skid_starting
Bool
db99.dbx2.2
Skid_running
Bool
db99.dbx2.3
Skid_stopping
Bool
db99.dbx2.4
Skid_in_CIP
Bool
db99.dbx2.5
Skid_SD_CIP
Bool
db99.dbx2.6
Skid_cancelling_CIP
Bool
db99.dbx2.7
Skid_in_purge
Bool
db99.dbx3.0
Skid_in_FS
Bool
db99.dbx3.1
FV_closed
Bool
db99.dbx3.2
PV_opened
Bool
db99.dbx3.3
Pump_Speed
real
db99.dbd4
0-100%
RPM
DInt
db99.dbd8
Feed_Pressure
real
db99.dbd12
DP_Pressure
real
db99.dbd16
Alarm_Word1
word
db99.dbw20
Alarm_Word2
word
db99.dbw22