Remote Operation
5-66
M370185-01
<delay_time> is a value in the range of 0.5-50 seconds. The unit of
second is the default and no units should be used with this parameter.
(Increments of 0.1seconds are allowed.).
The default value is 0.5 seconds.
Over Temperature Protection
The over temperature protection (OTP) is the alarm that protects the unit
in case of ventilation blockage, fan failure, or some other event that
causes the unit to overheat. The OTP cannot be masked to disable it. The
OTP alarm can have its output latch on clearing. See “Alarm Output
Latching” on page 3–23.
The SCPI command (s) for these instructions are:
[:]SYSTem[<channel(s)>]:PROTection:LATCh
The On setting shown by the front panel (“Using Over Temperature
Protection Lock (OTP)” on page 3–30), maps to having the OTP latch
flag set. The OFF setting maps to having the OTP latch flag cleared. The
default is to have the flag cleared.
Interlock Enable/Disable
The interlock feature is explained in “Interlock Function” on page 3–33.
Use the following command to enable and disable interlock. Enabling
interlock will allow the interlock feature to trigger based on the conditions
described in “Interlock Function” on page 3–33. This feature can only be
controlled using a SCPI command as there is no front panel equivalent.
The default value of the interlock is to be disabled.
Important:
The Interlock alarm cannot be masked or latched through the
alarm protection mechanisms. It can only be enabled or disabled using the
following command.
Commands:
[:]SENSe[<channel>]:INTerlock[:STATe] {?|ON|OFF}
Where
ON enables the use of interlock protection.
OFF disables the use of interlock protection.
Содержание Soresen XTR 100-8.5
Страница 2: ......
Страница 16: ...xiv ...
Страница 28: ...1 8 ...
Страница 50: ...Local Operation 3 8 M370185 01 Figure 3 3 Front Panel Menu System ...
Страница 93: ...Using Multiple Power Supplies M370185 01 3 51 3 ...
Страница 94: ...Local Operation 3 52 M370185 01 ...
Страница 128: ...Analog Programming APG and Isolated Analog Programming ISOL 4 34 M370185 01 ...
Страница 198: ...Remote Operation 5 70 M370185 01 ...
Страница 261: ...SCPI Command Tree M370185 01 A 35 A ...
Страница 262: ...A 36 ...
Страница 279: ...Index M370185 01 IX 3 described 3 7 3 36 number available 3 36 stored values 3 36 ...
Страница 280: ...IX 4 ...