4.5.7 System Response
The following is the definition of the response of the quench rate calculation
to the different combinations of actual sensor inputs.
key:
VVVV
= under range
^^^^
= over range
I
= in range valid readings
Link Dependant*
= the output will be driven either upscale (20mA) or
downscale (0 or 4mA) depending on the configuration
of the maths cards’ on-board link made by the user. See
document ‘Maths Function (Serial) User Guide’, Section
‘Maths Function Options’ for details.
Sensor 1
Sensor 2
System Display
System O/P
VVVV
VVVV
^^^^
0 or 4mA
I
VVVV
****
Link Dependant*
I
I
°/S
Equivalent Current
VVVV
I
****
Link Dependant*
^^^^
I
****
Link Dependant*
I
^^^^
****
Link Dependant*
^^^^
VVVV
****
Link Dependant*
VVVV
^^^^
****
Link Dependant*
^^^^
^^^^
^^^^
20mA