System Settings
Changing these settings will affect the operation of the heating/cooling system.
To view and edit these settings:
1. Press the
MENU button.
2. Press and hold the two middle buttons simultaneously until the
Installer Settings menu is displayed.
3. Scroll to System Settings and press the
Select button.
4. Scroll to the setting you want to change. Press the plus (
+) or minus (-) button to adjust the setting.
5. Press the
Done button when you are finished.
Î
Note on Delta Settings: The Delta T Setting is the delta, or difference between, the setpoint and current temp for determining when a
heat or cool call comes on. The “delta” is the number of degrees away from the setpoint.
Setting
Range
Default
Description
Mechanical
Settings
See next page
Balance Point
5-70 F
40 F
This is a user selectable value for when dual fuel “Restricted” mode is enabled. The
temperature selected is the compressor lockout temperature. When the outdoor
temperature is above this setpoint, only the heat pump will run for heating. When
the outdoor temperature is below this setpoint, only the furnace will run for heating.
Schedule Enable
Y or N
N
When enabled, the local thermostats scheduler function is enabled.
Recovery Enable
Y or N
Y
The Recover feature is active only when “Schedule” is enabled and the schedule
mode is set to “RUN”
Recovery operation, when enabled, will start the cooling or heating system so
that the desired comfort temperature is reached by the next scheduled set point
time. The advance start time calculation is a learned process that is recalculated
and adjusted each day until the room temperature is at the target temperature at
the schedule time. When the thermostat is in Recovery mode the display will show
“Recov”.
Recovery works for all scheduled periods (1-4) and in HEAT, COOL or AUTO
modes. While in Recovery the Aux-Heat stage will not engage.
The maximum Recovery time is one hour.
H/C Delta
3 - 15 degrees
3
Sets the minimum separation between heating and cooling setpoints. Attempts to
lower the cooling below the heating setpoint by this amount will PUSH the heating
setpoint down to maintain this separation. Same for setting the heating setpoint
above the cooling setpoint, it will PUSH the cooling setpoint up to maintain this
separation.
Heating Delta
Stage 1 ON
1 to 8 degrees
1
Sets the delta from setpoint that stage 1 heating starts.
Heating Delta
Stage 1 OFF
0 to 8 degrees
0
Sets the delta from setpoint that stage 1 heating stops. Stage 1 turns off at setpoint
minus (-) Delta Stage 1.
Heating Delta
Stage 2 ON
2 to 8 degrees
2
Sets the delta from setpoint that stage 2 heating starts.
Heating Delta
Stage 2 OFF
0 to 8 degrees
0
Sets the delta from setpoint that stage 2 heating stops. Stage 2 turns off at setpoint
minus (-) Delta Stage 2.
Heating Delta
Aux Heat ON
3 to 8 degrees
3
Sets the delta from setpoint that Aux Heat starts.
Heating Delta
Aux Heat OFF
0 to 8 degrees
0
Sets the delta from setpoint that stage 1 heating stops. Aux Heat turns off at
setpoint minus (-) Delta Aux Heat.
Cooling Delta
Stage 1 ON
1 to 8 degrees
1
Sets the delta from setpoint that stage 1 cooling starts.
Cooling Delta
Stage 1 OFF
-2 to 8 degrees
0
Sets the delta from setpoint that stage 1 Cooling stops. Stage 1 turns off at setpoint
plus (+) Delta Stage 1.
Cooling Delta
Stage 2 ON
2 to 8 degrees
2
Sets the delta from setpoint that stage 2 cooling starts.
Cooling Delta
Stage 2 OFF
-2 to 8 degrees
0
Sets the delta from setpoint that stage 2 Cooling stops. Stage 2 turns off at setpoint
plus (+) Delta Stage 2.