Mechanical Settings
Select
Type Heatpump
Fan Type Elec
C/O Type w/Cool
2nd Stage Heat N
Mechanical Settings
a.
Press the
MENU button twice.
b.
Press and hold the two inner buttons for 3 seconds to view
Installer Settings
c.
Scroll down to
System Settings and press the Select button.
d.
Scroll to
Mechanical Settings (it is the first option), then press
the
Select button.
e.
Choose option A-D below:
For Gas Furnace - Multistage Mechanical Settings
a.
Scroll down to 2nd Stage Heat.
b.
Press the + button to change the setting to Y for Yes.
c.
If your system also has 2nd stage cooling, scroll down to 2nd
Stage Cool and Press the + button to change the setting to Y for
Yes.
d.
Press the Done button 4 times and go to Perform System
Checkout.
For Electric Furnace Mechanical Settings
a.
Scroll down to Fan Type.
b.
Press the + button to change the setting Electric.
Î
If Single Stage System, press Done 4 times and go
to Perform System Checkout.
Î
If Multistage System, continue with steps c through f.
c.
Scroll down to 2nd Stage Heat.
d.
Press the + button to change the setting to Y for Yes.
e.
If your system also has 2nd stage cooling, scroll down to 2nd
Stage Cool and Press the + button to change the setting to Y for
Yes.
f.
Press the Done button 4 times and go to Perform System
Checkout.
Heat Pump Mechanical Settings
a.
Scroll to system Type.
b.
Press the + button to change the setting to Y to Heat Pump.
c.
Scroll down to Fan Type.
d.
Press the + button to change the setting to Electric.
e.
If Coleman, Rheem, or Rudd brand heat pump, scroll to C/O Type
and change to
With Heat.
Î
If Single Stage System, press Done 4 times and go
to Perform System Checkout.
Î
If Multistage System, continue with steps f through j.
f.
Scroll down to 2nd Stage Heat.
g.
Press the + button to change the setting to Y for Yes.
h.
Scroll down to 2nd Stage Cool.
i.
Press the + button to change the setting to Y for Yes.
j.
Press the Done button 4 times and go to Perform System
Checkout.
Enable Dual Fuel
a.
Scroll to system Type.
b.
Press the + button to change the setting type to Heatpump DF. The
default control mode is Non-restricted.
c.
To change to Restricted, scroll to DF Type Non-restricted. Press the
+ button to set the mode to Restricted.
d.
If Non-restricted control mode was selected, press the Done button
4 times and go to Perform System Checkout.
e.
If restricted control mode was selected, set the desired compressor
lockout temperature. Press the Done button 3 times then select
User Settings. Scroll down to Balance Point. Use the + and
- buttons to set the compressor lockout temperature. Default
compressor lockout temperature is 40°F.
f.
Press the Done button 2 times and go to Perform System Checkout.