2. ELECTRICAL SERVICE SPECIFICATIONS
A. Gas and Steam Models
IMPORTANT:
Figures shown are for non-reversing models ONLY. For reversing models contact the
factory.
IMPORTANT:
The dryer
must be
connected to the electric supply shown on the data label that is
affixed to the back side of the upper/top control door. In the case of 208 VAC or
230/240 VAC, the supply voltage
must match
the electric service specifications of
the data label exactly.
IMPORTANT:
The wire size
must be
properly sized to handle the related current.
WARNING: 208 VAC and 230/240 VAC ARE NOT THE SAME.
Any damage done to dryer
components due to improper voltage connections will automatically VOID THE
WARRANTY.
NOTE: ADC
reserves the right to make changes in specifications at any time, without notice or
obligation.
MLG-75 (Gas)
MLS-75 (Steam)
E
LECTRICAL
S
ERVICE
S
PECIFICATIONS
(
PER DRYER
)
IMPORTANT: 208 VAC and 230/240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTE:
A. Fuse ratings are dual-element, time-delay, current limiting, class RK1 or RK5 ONLY.
B. Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify correct breaker
size according to appliance amp draw rating and type of breaker used.
C.
Circuit breakers for 3Ø dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
MINIMUM
WIRE SIZE*
FUSING
Dual Element
Time Delay
CIRCUIT
BREAKER
120 (60 Hz)
1
2
13
10
20
25
208 (60 Hz)
1
2
8
14
12
15
208 (60 Hz)
3
3/4
5
14
8
15
240 (50/60 Hz)
3
3/4
5
14
8
15
240 (50/60 Hz)
1
2
7
14
12
15
380-400 (50 Hz)
3
3/4
3
14
5
15
416 (50 Hz)
3
3/4
3
14
5
15
460 (60 Hz)
3
3/4
3
14
5
15
* AWG Stranded Wire ... for individual lenghts less than 100 feet.