10
American Dryer Corp.
113235 - 5
D. FRESH AIR SUPPLY REQUIREMENTS
The dryer air supply (make-up air)
must be
given careful consideration to ensure proper performance of each
dryer. An unrestricted source of air is necessary for each dryer. An airflow of 375 cfm (cubic feet per minute)
(11 cmm [cubic meters per minute])
must be
supplied to each gas dryer. As a general rule, an unrestricted air
entrance from the outdoors (atmosphere) of a minimum of 1 square foot (0.09 square meters) is required for
each dryer. If registers or louvers are installed over the openings, then the area
must be
increased. It is not
necessary to have a separate make-up air opening for each dryer. Common make-up air openings are acceptable.
However, they
must be
set up in such a manner that the make-up air is distributed equally to the dryers. The
dryer
must be
installed with provisions for adequate combustion and make-up air supply.
EXAMPLE
: For a bank of eight (8) dryers, two (2) unrestricted openings measuring 2 feet by 2 feet
(0.61 meters by 0.61 meters) are acceptable.
IMPORTANT:
Make-up air openings
should not be
located in an area directly near where
exhaust vents exit the building.
Allowances
must be
made for remote or constricting passageways or where dryers are located at excessive
altitudes or predominantly low pressure areas.
IMPORTANT:
Make-up air
must be
provided from a source free of dry cleaning solvent fumes.
Make-up air that is contaminated by dry cleaning solvent fumes will result in
irreparable damage to the motors and other dryer components.
NOTE:
Component failure due to dry cleaning solvent fumes will VOID THE WARRANTY.
Содержание AD-285
Страница 48: ...ADC Part No 113235 5 07 10 08 7...