NOTE:
As per the National Fuel Gas Code, “Exhaust ducts for type 2 clothes dryers shall be
constructed of sheet metal or other noncombustible material. Such ducts shall be
equivalent in strength and corrosion resistance to ducts made of galvanized sheet steel
not less than 26 gauge (0.0195-inches [0.50 mm]) thick.”
SINGLE DRYER VENTING
IMPORTANT:
For exhaust duct runs over 40 feet (12 meters) a minimum size of 10-inches
(25.4 cm)
must be
used.
HORIZONTAL VENTING
When horizontal single 8-inch (20.32 cm) venting is used, the ductwork to the outlet
cannot
exceed 40 feet (12
meters) refer to
Illus. A below
. This calculation of 40 feet (12 meters) compensates or allows for the use of a
maximum of two (2) elbows.
Illus. A