25 MAY 2009
Page 33
000744MAN-02
COMPRESSOR TROUBLESHOOTING
Fault
Possible Cause
Verification
Recommended Action
Compressor will
not start
Manual High pressure
control tripped.
Press the button on the control, it
will click when pressed.
Proceed to Operation Trouble-
shooting.
Faulty control board.
Hi and Low LED’s off, HB is flashing
but Y LED is not on, or no 24VAC
across Y and C of bottom right con-
nector.
Replace control board.
Faulty run capacitor.
(Single phase only)
Check value with capacitance meter.
Should match label on capacitor.
Compressor will hum while trying to
start and then trip its overload.
Replace if faulty.
Loose or faulty wiring.
Check all compressor wiring, includ-
ing inside compressor electrical box.
Fix any loose connections. Re-
place any damaged wires.
Faulty compressor
contactor.
Voltage on line side with contactor
held closed, but no voltage on one
or both terminals on the load side.
Points pitted or burned.
Or, 24VAC across coil but contactor
will not engage.
Replace contactor.
Thermal overload on
compressor tripped.
Ohmmeter shows reading when
placed across R and S terminals
and infinity between C & R or C & S.
A valid resistance reading is present
again after the compressor has
cooled down.
Proceed to Operation Trouble-
shooting to determine the cause
of the thermal overload trip.
Burned out motor.
(open winding)
Remove wires from compressor.
Ohmmeter shows infinite resistance
between any two terminals Note: Be
sure compressor overload has had a
chance to reset. If compressor is hot
this may take several hours.
Replace the compressor.
Burned out motor
(shorted windings)
Remove wires from compressor.
Resistance between any two termi-
nals is below the specified value.
Replace the compressor.
Motor shorted to ground.
Remove wires from compressor.
Check for infinite resistance be-
tween each terminal and ground.
If any terminal to ground is not
infinite replace the compressor.
Seized compressor due to
locked or damaged
mechanism.
Compressor attempts to start but
trips its internal overload after a few
seconds. (Run capacitor already
verified)
Attempt to “rock” compressor
free. If normal operation cannot
be established, replace
compressor.
Compressor
starts hard
Start capacitor faulty.
(Single phase only)
Check with capacitance meter.
Check for black residue around
blowout hole on top of capacitor.
Replace if faulty.
Remove black residue in electri-
cal box if any.
Potential Relay faulty.
(Single phase only)
Replace with new one and verify
compressor starts properly.
Replace if faulty.
Compressor is “tight” due
to damaged mechanism
Compressor attempts to start but
trips its internal overload after a few
seconds. Run capacitor has been
verified already.
Attempt to “rock” compressor
free. If normal operation cannot
be established, replace compres-
sor.
Compressor
Stage 2 will not
activate
Faulty Stage 2 module.
Verify if 24VAC is present across
Y2 and C of the terminal strip.
Replace module if signal is pre-
sent. Check wiring if signal is not
present.
Содержание Copper Series
Страница 9: ...25 MAY 2009 Page 9 000744MAN 02...
Страница 10: ...Page 10 000744MAN 02 25 MAY 2009...
Страница 13: ...25 MAY 2009 Page 13 000744MAN 02...
Страница 16: ...Page 16 000744MAN 02 25 MAY 2009...
Страница 18: ...Page 18 000744MAN 02 25 MAY 2009...
Страница 19: ...25 MAY 2009 Page 19 000744MAN 02...
Страница 20: ...Page 20 000744MAN 02 25 MAY 2009...
Страница 22: ...Page 22 000744MAN 02 25 MAY 2009...
Страница 45: ...25 MAY 2009 Page 45 000744MAN 02 REFRIGERATION CIRCUIT DIAGRAMS...
Страница 46: ...Page 46 000744MAN 02 25 MAY 2009 REFRIGERATION CIRCUIT DIAGRAMS continued...
Страница 47: ...25 MAY 2009 Page 47 000744MAN 02 REFRIGERATION CIRCUIT DIAGRAMS continued...
Страница 53: ...25 MAY 2009 Page 53 000744MAN 02 ELECTRICAL DIAGRAMS 230 1 60...
Страница 54: ...Page 54 000744MAN 02 25 MAY 2009 ELECTRICAL DIAGRAMS 230 1 60 continued...
Страница 55: ...25 MAY 2009 Page 55 000744MAN 02 CASE DETAILS Front View Back View Left Side View Right Side View...
Страница 56: ...Page 56 000744MAN 02 25 MAY 2009 Top View Size 2 3 4 Ton CASE DETAILS continued Top View Size 5 Ton...
Страница 58: ...Page 58 000744MAN 02 25 MAY 2009...
Страница 59: ...25 MAY 2009 Page 59 000744MAN 02...