Page 44
000744MAN-02
25 MAY 2009
PUMP DOWN PROCEDURE
STEP 1
Connect the refrigerant recovery unit to the heat pump service ports via a refrigeration charging manifold
and to a recovery tank as per the instructions in the recovery unit manual.
If there was a compressor
burn out, the refrigerant cannot be reused and must be disposed of according to local codes.
STEP 2
Ensure all hose connections are properly purged of air. Start the refrigerant recovery as per the instructions
in the recovery unit manual.
STEP 3
Allow the recovery unit suction pressure to reach a vacuum. Once achieved, close the charging manifold
valves. Shut down, purge and disconnect the recovery unit as per the instructions in its manual. Ensure the
recovery tank valve is closed before disconnecting the hose to it.
STEP 4
Connect a nitrogen tank to the charging manifold and add nitrogen to the heat pump until a positive pres-
sure of 5-10PSIG is reached. This prevents air from being sucked into the unit by the vacuum when the
hoses are disconnected.
STEP 5
The heat pump is now ready for repairs. Always ensure nitrogen is flowing through the system during any
soldering procedures to prevent soot buildup inside the pipes. AMERICAN DREAM Geothermal recom-
mends replacing the liquid line filter-drier anytime the refrigeration system has been exposed to the atmos-
phere.
VACUUM AND CHARGING PROCEDURE
STEP 1
After completion of repairs and nitrogen pressure testing, the refrigeration circuit is ready for vacuuming.
STEP 2
Release the refrigerant circuit pressure and connect the vacuum pump to the charging manifold. Start the
vacuum pump and open the charging manifold valves. Vacuum until the vacuum gauge remains at less
than 500 microns for at least 1 minute with the vacuum pump valve closed.
STEP 3
Close the charging manifold valves then shut off and disconnect the vacuum pump. Place a refrigerant tank
with the proper refrigerant on a scale and connect it to the charging manifold. Purge the hose to the tank.
STEP 4
Weigh in the appropriate amount of refrigerant through the low pressure (suction) service port. Refer to the
label on the unit or the
Charging The system
section for the proper charge amount.
STEP 5
If the unit will not accept the entire charge, the remainder can be added through the low pressure service
port after the unit has been restarted.
REPLACMENT PROCEDURE FOR A COMPRESSOR BURN-OUT
STEP 1
Pump down the unit as per the Pump Down Procedure above.
STEP 2
Replace the compressor. Replace the liquid line filter-drier.
STEP 3
Vacuum the unit until it remains under 500 microns for several minutes with the vacuum pump valve closed.
STEP 4
Charge the unit and operate it for continuously for 2 hours. Pump down the unit and replace the filter-drier.
Vacuum the unit until it remains under 500 microns for several minutes with the vacuum pump valve closed.
STEP 5
Charge the unit (refrigerant can be re-used) and operate it for 2-3 days. Pump down the unit and replace
the filter-drier.
STEP 6
Charge the unit (refrigerant can be re-used) and operate it for 2 weeks. Pump down the unit and replace
the filter-drier.
STEP 7
Charge the unit a final time. Unit should now be clean and repeated future burn-outs can be avoided.
REPAIR PROCEDURES
Содержание Copper Series
Страница 9: ...25 MAY 2009 Page 9 000744MAN 02...
Страница 10: ...Page 10 000744MAN 02 25 MAY 2009...
Страница 13: ...25 MAY 2009 Page 13 000744MAN 02...
Страница 16: ...Page 16 000744MAN 02 25 MAY 2009...
Страница 18: ...Page 18 000744MAN 02 25 MAY 2009...
Страница 19: ...25 MAY 2009 Page 19 000744MAN 02...
Страница 20: ...Page 20 000744MAN 02 25 MAY 2009...
Страница 22: ...Page 22 000744MAN 02 25 MAY 2009...
Страница 45: ...25 MAY 2009 Page 45 000744MAN 02 REFRIGERATION CIRCUIT DIAGRAMS...
Страница 46: ...Page 46 000744MAN 02 25 MAY 2009 REFRIGERATION CIRCUIT DIAGRAMS continued...
Страница 47: ...25 MAY 2009 Page 47 000744MAN 02 REFRIGERATION CIRCUIT DIAGRAMS continued...
Страница 53: ...25 MAY 2009 Page 53 000744MAN 02 ELECTRICAL DIAGRAMS 230 1 60...
Страница 54: ...Page 54 000744MAN 02 25 MAY 2009 ELECTRICAL DIAGRAMS 230 1 60 continued...
Страница 55: ...25 MAY 2009 Page 55 000744MAN 02 CASE DETAILS Front View Back View Left Side View Right Side View...
Страница 56: ...Page 56 000744MAN 02 25 MAY 2009 Top View Size 2 3 4 Ton CASE DETAILS continued Top View Size 5 Ton...
Страница 58: ...Page 58 000744MAN 02 25 MAY 2009...
Страница 59: ...25 MAY 2009 Page 59 000744MAN 02...