background image

25 MAY 2009 

Page   21 

000744MAN-02 

LINE SET INTERCONNECT TUBING  

Once the outside loops have been installed and run into 

the building, the piping to the ports on the unit can be 
constructed.  Each line set has a liquid line and a vapour line.  
The vapour line is 1/2”  (OD) and the liquid line is 1/2” (OD).  For 
horizontal loops, both lines are 1/2” (OD), reduce one of the 
lines in each line set down to 3/8” (OD) before running the lines 
over to the heat pump.  These reduced lines will be the liquid 
line for each line set.   

 
Do a final pressure check on each line set and then 

remove the pressure and cut the ends off the lines.  The heat 
pump has ports labeled Liquid 1 to 5 and Vapour 1 to 5.  Run 
each line set over to the designated ports on the heat pump.  
Refer to 

Diagram 000769CDG 

for more information on how to 

connect to the heat pump. 

 
The tubing used for this procedure must be refrigeration 

tubing (cleaned & dehydrated) suitable for the job. Every effort 
must also be made to insure that the tubing does not become 
contaminated during installation. We recommend that caps be 
placed on the open ends of tubing immediately after cuts are 
made and that these caps are only removed after all bends have 
been made and the pipe fixed in its permanent location ready to 
make the silver soldered joints. It is very important to keep a 
refrigeration system perfectly clean and dry.  Removing the caps 
just prior to silver soldering will ensure minimum exposure to  
the humidity in the atmosphere. 

 

PIPE INSULATION 

     All line set piping  inside the structure (between the 

structure entry point and the heat pump) should be insulated 
with 3/8”  thick closed cell pipe insulation  to prevent 
condensation and dripping onto floors or walls during the 
heating season.   It can be slid onto the capped tubing without 
having to slice it down the side.  Ensure that any joints in in the 
line sets are accessible for leak testing. 

 

     Liquid and Vapour ports and any remaining exposed tubing 
should be insulated with 3/8”  thick closed cell pipe insulation 
once the silver soldering and pressure testing is complete.  
Ensure that all individual pieces of pipe insulation are glued to 
each other so there are no air gaps.    

 

SILVER SOLDERING LINE SETS  

Once all the line sets have been routed, insulated and 

fastened in place, the connections to the heat pump ports can 
be made.  Remove the pressure from the heat pump and cut the 
ends off of the Liquid and Vapour ports.  Remove the caps from 
the line set tubing.  The line sets can be connected to the ports 
on the heat pump using couplings, or alternately the tubing can 
be "swaged".  The joints should be silver soldered with 5% 
silfos. 

 
 

AMERICAN DREAM Geothermal absolutely requires 

that dry nitrogen be bled through the system during all 
silver soldering procedures so that no oxidation occurs on 
the inside of the copper tubing.  

The service ports on the unit 

can be used to connect the nitrogen with a refrigeration 
manifold. 

 
If necessary, a damp clothe can be wrapped around the 

each of the ports to prevent melting the grommet when silver 

soldering.  Ensure that no water enters any of the ports or 
tubing. 

PRESSURE TESTING 

Once all connections are complete, the system should be 

pressure tested to 

100PSIG (690kPa)

 with dry nitrogen.  Check 

all joints at the unit and any made in the interconnect tubing for 
leaks using soap suds, Spray nine, etc.  It is important not to 
bypass this step as vacuuming the system with a leak will be 
impossible and attempting to do so will introduce moisture into 
the system, making the vacuum process take much longer than 
if the leak had been found and repaired first. 

 

VACUUMING THE SYSTEM 

Remove the pressure from the system and connect the 

vacuum pump to the refrigeration manifold.  Tighten all hose 
connections, open the valves on the manifold and start the 
vacuum pump.   

  
Vacuum the system until the reading on an electronic 

vacuum gauge remains below 500 microns for a period of 5 
minutes after the vacuum pump is shut off and the system 
sealed.   

CHARGING THE SYSTEM 

Once the system has been vacuumed, refrigerant can be 

added by weighing in 1/3 of the prescribed refrigerant charge 
into the low side of the system. Start the heat pump in the 
heating mode and continue to add refrigerant as a liquid at a 
rate of no more than 1 lb. per minute until the prescribed charge 
is reached. 

 
Alternately, before the machine is started, the entire 

charge can be weighed into the system through the high side of 
the system.  

TABLE 16 

shows the typical charge per unit size.  

This allows for: 

 

     20ft of distance (40ft of pipe) interconnect tubing from     

       the unit to the wall,  

 

20ft of distance from the wall to the borehole /trench,  

 

a standard loop (100ft borehole or 150ft trench).   

  
Additional refrigerant is required as per 

TABLE 16 

if the 

installation exceeds these parameters.   

Loop Connection & Charging 

TABLE 16 - Charge Chart    

Model

 

Size (tons) 

Lbs.

 

kg 

45 

12 

5.4 

55 

16 

7.3 

65 

20 

9.1 

Extra loop (borehole) 

0.5 

Extra loop (trench) 

1.5 

0.7 

Extra distance to borehole 
Extra depth of borehole 
Extra distance to trench 
Extra length of trench 
Extra distance in structure 

0.1oz per foot 

0.003 

Содержание Copper Series

Страница 1: ...Vegas Nevada 89169 AMERICAN DREAM Freon Copper Series Triple Function Installation and Service Manual Email info AmericanDreamGeothermal com Web www AmericanDreamGeothermal com Document Number 000744M...

Страница 2: ...ced A fire extinguisher and proper ventilation should be present whenever brazing is performed CAUTION Venting refrigerant to atmosphere is illegal A proper refrigerant recovery system must be employe...

Страница 3: ...INDOOR COIL FAN CASE REVISIONS 3 Ton HACW P 1 T BLANK or H C or Z SDETV 02 2 T 02 6 S 02 7 T 02 4 Ton HACW P 1 T BLANK or H C or Z SDETV 02 2 T 02 6 S 02 7 T 02 5 Ton P BLANK or H C or Z SDETV HACW 1...

Страница 4: ...l Page 15 Hydronic System Connections Page 15 Duct Sizing Guide Page 17 Freon Copper LOOP CONNECTION AND CHARGING PAGE 21 Line Set Interconnect Tubing Page 21 Pipe Insulation Page 21 Silver Soldering...

Страница 5: ...Ratings Hydronic Heating 60Hz Page 48 Table 21 Heat Pump Electrical Information 230 1 60 Page 52 Table 22 Heat Pump Electrical Information 208 3 60 Page 52 Table 23 Heat Pump Electrical Information 2...

Страница 6: ...talled with the removable end where the filter is inserted on either side to facilitate changing the filter ELECTRICAL CONNECTIONS The heat pump has a concentric 1 093 0 875 knockout for power supply...

Страница 7: ...er of the plenum heater for more information NOTE Some models are not available in two stage at the pre sent time see Electrical Tables The Y2 signal is not used for these units INDOOR LOOP CIRCULATOR...

Страница 8: ...ures equalize in the unit The unit may restart after the timer period has expired Should the unit trip on the safety con trol again the compressor will once again shut down and the counter will be inc...

Страница 9: ...25 MAY 2009 Page 9 000744MAN 02...

Страница 10: ...Page 10 000744MAN 02 25 MAY 2009...

Страница 11: ...7 As the transition from summer to fall begins and the cool ing load is greatly reduced the loops begin to cool down on their own Eventually a point is reached at which the loops are cooled down enou...

Страница 12: ...he COP must be unlocked by command U before using command C to change system settings The list of settings for command C is shown in TABLE 11 It is recommended that the settings be left at the default...

Страница 13: ...25 MAY 2009 Page 13 000744MAN 02...

Страница 14: ...EAT PUMP SIZING TABLE 12 depicts averages WILL VARY WITH ENVELOP EFFICIENCY as a rough guideline to the size of home each heat pump size can handle THE TABLE ABOVE IS FOR INFORMATION ONLY IT SHOULD NO...

Страница 15: ...pass through it to prevent any hot spots in the heater elements TABLE 14 shows the recommended size plenum heater as well as the wire size and breaker size needed to provide power to the plenum heate...

Страница 16: ...Page 16 000744MAN 02 25 MAY 2009...

Страница 17: ...6 15 x 15 20 684 201 1750 18 8 x 40 10 x 30 12 x 24 14 x 20 16 x 17 16 5 x 16 5 20 826 254 2000 18 8 x 40 10 x 30 12 x 24 14 x 20 16 x 17 16 5 x 16 5 22 944 254 2250 20 10 x 38 12 x 30 14 x 26 16 x 22...

Страница 18: ...Page 18 000744MAN 02 25 MAY 2009...

Страница 19: ...25 MAY 2009 Page 19 000744MAN 02...

Страница 20: ...Page 20 000744MAN 02 25 MAY 2009...

Страница 21: ...ine set tubing The line sets can be connected to the ports on the heat pump using couplings or alternately the tubing can be swaged The joints should be silver soldered with 5 silfos AMERICAN DREAM Ge...

Страница 22: ...Page 22 000744MAN 02 25 MAY 2009...

Страница 23: ...ation Record the type of antifreeze and the mixture value on the startup sheet circle Vol or Weight 4 Record the static loop pressure on the startup sheet Line Sets Inside structure 1 Verify that all...

Страница 24: ...l box and compressor 4 Adjust the thermostat setpoint to the desired room temperature and let the unit run through a cycle Record the setpoint and the discharge pressure when the unit shuts off 5 For...

Страница 25: ...connections are correct and securely fastened Circuit breaker or fuse size and wire gauge for Heat Pump A Ga Circuit breaker or fuse size wire gauge and Plenum Heater size A Ga kW Low voltage connect...

Страница 26: ...oop Out Hot Out temperature 7 Indoor Delta T should be between 8 12 F 4 6 C 8 Compressor L1 C current black wire place meter between electrical box and compressor 4 Adjust the aquastat setpoint to the...

Страница 27: ...aker or fuse size wire gauge and Plenum Heater size A Ga kW Low voltage connections are correct and securely fastened Unit Charge Refrigerant charge be fore power is turned on Lbs kg STARTUP DATA Prep...

Страница 28: ...ction at the top of the adjustment record sheet Circle F or C at the top right 2 Record all data for the initial readings elapsed time 0 Adjust the TXV for the loop that is the furthest out Record the...

Страница 29: ...lation Site City Province Country Serial Installer Company Date Model F C TIME COMMON LOOP 1 LOOP 2 LOOP 3 LOOP 4 LOOP 5 LOOP 6 ADJUSTMENT Actual EL S ET D P1 V1 S1 P2 V2 S2 P3 V3 S3 P4 V4 S4 P5 V5 S5...

Страница 30: ...lter 6 months Inspect for dirt Replace if necessary Contactor 1 year Inspect for pitted or burned points Replace if necessary Condensate Drain 1 year Inspect for clogs Remove and clean if necessary Ci...

Страница 31: ...roceed to POWER SUPPLY TROUBLESHOOTING otherwise proceed to STEP 2 STEP 2 Remove the door and electrical box cover and check to see if the HI or LOW LED s are flashing or on Record The results Turn th...

Страница 32: ...AC signal present across C and Stage 1 of the thermo stat Correct the setup Faulty thermostat to heat pump wiring 24VAC signal present across Stage 1 and C of the thermostat but not pre sent across Y1...

Страница 33: ...infinite resistance between any two terminals Note Be sure compressor overload has had a chance to reset If compressor is hot this may take several hours Replace the compressor Burned out motor shorte...

Страница 34: ...Pressure Heating TXV s adjusted too far closed Verify superheat It should be be tween 8 14 F 3 8 C Superheat will be high if TXV is closed too far Adjust TXV to obtain 8 14 F 3 8 C superheat Low Sucti...

Страница 35: ...e or more heating TXV s stuck too far open Adjusting the TXV does not affect the superheat of the loop or the suc tion pressure Low super heat low discharge pressure Adjust the TXV all the way in and...

Страница 36: ...g S and S does not cause the Loop Switch LED to come on or does not cause a loop change Replace the control board High Pressure control and man ual high pressure control trips very fast Faulty reclaim...

Страница 37: ...ir flow are good but suction is low Check static refrigeration pressure of unit for very low value Locate the leak and repair it Spray nine a sniffer and dye are common methods of locating a leak Leak...

Страница 38: ...en White pin 3 and the following at the fan con trol signal harness insert probes in connector where wire is inserted do not unplug the connector Circulation Grey pin 15 Stage 1 Yellow pin 6 Stage 2 Y...

Страница 39: ...at to DXTF Control Box wiring 24VAC not present across Stage 1 C and COM of the aquastat Correct or replace wiring Faulty aquastat to DXTF Control Box wiring 24VAC signal present across Stage 1 NO and...

Страница 40: ...he discharge pressure reduces Surging Discharge Pressure Heating TXV s adjusted too far closed Verify superheat It should be be tween 8 14 F 3 8 C Superheat will be high if TXV s are closed too far Ad...

Страница 41: ...F 3 8 C superheat One or more heating TXV s stuck too far open Adjusting the TXV does not affect the superheat of the loop or the suc tion pressure Low super heat low discharge pressure Attempt to adj...

Страница 42: ...anual Faulty thermostat Thermostat doesn t indicate a call for auxiliary or emergency when it should Replace thermostat Faulty thermostat Thermostat indicates auxiliary or emergency but no 24VAC signa...

Страница 43: ...spect the pump to see if shaft is turning Use an amprobe to measure current draw Replace if faulty Insufficient hot water Heat Pump Prob lem Blockage or restriction in the water line or hot water heat...

Страница 44: ...gerant circuit pressure and connect the vacuum pump to the charging manifold Start the vacuum pump and open the charging manifold valves Vacuum until the vacuum gauge remains at less than 500 microns...

Страница 45: ...25 MAY 2009 Page 45 000744MAN 02 REFRIGERATION CIRCUIT DIAGRAMS...

Страница 46: ...Page 46 000744MAN 02 25 MAY 2009 REFRIGERATION CIRCUIT DIAGRAMS continued...

Страница 47: ...25 MAY 2009 Page 47 000744MAN 02 REFRIGERATION CIRCUIT DIAGRAMS continued...

Страница 48: ...0 802 3 375 43 500 12 7 3 78 65 5 Stage 1 1700 802 2 930 41 900 12 3 4 19 Stage 2 2100 991 4 180 53 300 15 6 3 74 Table 19 Standard Capacity Ratings Cooling 60Hz EAT 80 F 26 7 C STAGE 1 LIQUID LINE 68...

Страница 49: ...g Mode Source Data Indoor Loop Power Consumption Sink Data Outdoor Loop Suct Pres Evap Temp EAT Air Flow LAT Delta T Latent Sensible HAB Compressor Fan Total Electrical Efficiency Disch Pres Cond Temp...

Страница 50: ...0 Hz Cooling Mode Source Data Indoor Loop Power Consumption Sink Data Outdoor Loop Suct Pres Evap Temp EAT Air Flow LAT Delta T Latent Sensible HAB Compressor Fan Total Electrical Efficiency Disch Pre...

Страница 51: ...Hz Cooling Mode Source Data Indoor Loop Power Consumption Sink Data Outdoor Loop Suct Pres Evap Temp EAT Air Flow LAT Delta T Latent Sensible HAB Compressor Fan Total Electrical Efficiency Disch Pres...

Страница 52: ...58 3 5 16 9 20 0 30 10 4 55 15 0 88 4 0 20 0 23 8 40 8 4 65 19 6 123 5 5 26 1 31 0 50 8 4 Models are single stage Table 23 Heat Pump Electrical Information 220 1 50 Model Compressor Fan FLA MCA Max F...

Страница 53: ...25 MAY 2009 Page 53 000744MAN 02 ELECTRICAL DIAGRAMS 230 1 60...

Страница 54: ...Page 54 000744MAN 02 25 MAY 2009 ELECTRICAL DIAGRAMS 230 1 60 continued...

Страница 55: ...25 MAY 2009 Page 55 000744MAN 02 CASE DETAILS Front View Back View Left Side View Right Side View...

Страница 56: ...Page 56 000744MAN 02 25 MAY 2009 Top View Size 2 3 4 Ton CASE DETAILS continued Top View Size 5 Ton...

Страница 57: ...H STAGE 2 STAGE 1 FAN ONLY Recirculation Model Nom Size Full Reduced Full Reduced Full Reduced Tons CFM L s CFM L s CFM L s CFM L s CFM L s CFM L s 25 2 848 400 721 340 721 340 613 289 475 224 404 191...

Страница 58: ...Page 58 000744MAN 02 25 MAY 2009...

Страница 59: ...25 MAY 2009 Page 59 000744MAN 02...

Страница 60: ...only to the completely finished and insulated structure Startup of the unit shall not be scheduled prior to completion of construction and final duct installation for validation of this warranty 4 It...

Отзывы: