background image

25 MAY 2009 

Page   7 

000744MAN-02 

 
 
 

TABLE 3 

shows typical settings for the aquastat. 

 

The 

settings may be changed as desired; however, the setpoint 

should not exceed 

120°F (49°C)

; Exceeding this setpoint limit 

will cause the heat pump operating pressures to approach the 
safety control settings, possibly causing nuisance shut downs. 

  

If only floor zones are being heated, it is highly rec-

ommended to drop each of the setpoints by 15°F (8°C) for 
increased efficiency. 

 
It is recommended that a buffer tank with electric elements 

be selected to provide auxiliary / backup heat.   The tank ele-
ment thermostats can be set to a low value of around 60°F   
(15°C) which will prevent the hydronic system from becoming 
too cold should there be a failure in the heating system. 

 

Drawing 000344CDG 

shows how a typical zone system 

would be setup with the FCTF unit.  The zone controls and heat 
pump operate independently, there are no connections between 
the two systems.

   

TWO STAGE CONTROL BOX 

The Two Stage Control Box is the interface between the 

controls (thermostat and aquastat) and the heat pump.  It’s main 
function is to provide the signal manipulation required to operate 
the fan or the Indoor Loop Circulator as required based on the 
signals received from the controls.  It also contains a contactor 
for power connections to the Indoor Loop Circulator.   

 
The connections between the  control box and the heat 

pump are shown in 

TABLE 4

.  Three documents are shipped 

with the Control Box:  

000739SCH,  000740CDG and 

000741INF

.  They contain all the information required to com-

plete the Two Stage Control Box connections, as well as infor-
mation on how the control box operates. 

AIR FLOW REDUCTION AND            

PLENUM HEATER CONNECTIONS 

TABLE 5 

lists the remaining four terminals on the heat 

pump terminal strip.  These signals are separate from the Con-
trol Box.  The AR

1

 and AR

2

 terminals are the airflow reduction 

signal.  See the 

FAN MOTOR 

section for more information on 

therm.  The I and 1 terminals are the dry contacts for the plenum 

heater.  Connect these to the C and 1 terminals of the plenum 
heater.  Refer to the electrical box diagram (ELB) of the heat 
pump or the diagram on the cover of the plenum heater for more 
information.    

NOTE: 

Some models are not available in two-stage at the pre-

sent time (see 

Electrical Tables

).  The Y2 signal is not used for 

these units

 

INDOOR LOOP CIRCULATOR WIRING 

The Indoor Loop circulator provides flow between the heat 

pump and the buffer tank.  The Two Stage Control Box has pro-
visions for connecting the Indoor Circulator so that it will be 
turned on whenever the heat pump is in water heat mode and 
the compressor operates.  Connect line voltage (115 or 
230VAC) to the terminals marked L1 and L2 of the Indoor Circu-
lator Contactor.  Connect the Indoor Loop circulator to the termi-
nals marked P1 and P2.  Ensure that the line voltage and circu-
lator voltage rating are the same.

 

FAN MOTOR

 

The unit is equipped with a direct drive ECM fan motor for 

maximum efficiency.  The motor features a soft start which fur-
ther improves efficiency by eliminating inrush current and pro-
vides a smooth, quiet ramp up to speed .  The motor will main-
tain the programmed air flow up to the maximum external static 

value.

 

Refer to the 

APPENDIX A:  ECM Fan Airflow Tables.  

 
The air flow can be set to four different levels by changing 

the position on the Air Flow board located in the electrical box.  
The four levels are indicated in 

TABLE 6

.  The actual air flow 

TABLE 6 - Airflow Selections 

Position

 

Airflow

 

LOW 

-12% 

MED 

-6% 

HIGH 

Nominal 

MAX 

+6% 

TABLE 4 - 

FCTF Two Stage Control Box to Heat 

Pump Signals  

Signal

 

Description

 

24VAC Common (Ground) 

Fan low speed (for air circulation) 

Y

1

  

Heat Pump Stage 1 (Compressor stage 1) 

R

H

 

24VAC Hot 

Fault (24VAC when fault condition) 

W

2

 

Heat Pump Stage 3 (auxiliary heat) / Emergency 
Heat 

O/B/W

1

 

Cooling Mode (reversing valve) 

Y

2

  

Heat Pump Stage 2 (Compressor stage 2 

E1 

Fan Auxiliary/Emergency Speed Control (In) 

E2 

Fan Auxiliary/Emergency Speed Control (Out) 

FC 

Fan Contactor 

TABLE 5 - Remaining Signal Descriptions  

Signal

 

Description

 

AR

1

 

Airflow Reduction*   

AR

2

 

Airflow Reduction* 

Plenum Heater dry contact  

Plenum Heater dry contact 

Connect AR

1

 to AR

2

 with a dry contact  to reduce the airflow 

by 15%.  Refer to the 

Fan Motor 

sub-section for more infor-

mation. 

TABLE 3 - Typical Aquastat Settings 

 

Stage 1** 

 

Stage 2**  

Item

 

°

°

°F 

°C 

Setpoint 

115 

46 

105 

41 

Delta 

Activation * 

110 

43 

100 

38 

*Activation is indirectly set by the Setpoint and Delta values  
** All values must be set identical for both stages 

Содержание Copper Series

Страница 1: ...Vegas Nevada 89169 AMERICAN DREAM Freon Copper Series Triple Function Installation and Service Manual Email info AmericanDreamGeothermal com Web www AmericanDreamGeothermal com Document Number 000744M...

Страница 2: ...ced A fire extinguisher and proper ventilation should be present whenever brazing is performed CAUTION Venting refrigerant to atmosphere is illegal A proper refrigerant recovery system must be employe...

Страница 3: ...INDOOR COIL FAN CASE REVISIONS 3 Ton HACW P 1 T BLANK or H C or Z SDETV 02 2 T 02 6 S 02 7 T 02 4 Ton HACW P 1 T BLANK or H C or Z SDETV 02 2 T 02 6 S 02 7 T 02 5 Ton P BLANK or H C or Z SDETV HACW 1...

Страница 4: ...l Page 15 Hydronic System Connections Page 15 Duct Sizing Guide Page 17 Freon Copper LOOP CONNECTION AND CHARGING PAGE 21 Line Set Interconnect Tubing Page 21 Pipe Insulation Page 21 Silver Soldering...

Страница 5: ...Ratings Hydronic Heating 60Hz Page 48 Table 21 Heat Pump Electrical Information 230 1 60 Page 52 Table 22 Heat Pump Electrical Information 208 3 60 Page 52 Table 23 Heat Pump Electrical Information 2...

Страница 6: ...talled with the removable end where the filter is inserted on either side to facilitate changing the filter ELECTRICAL CONNECTIONS The heat pump has a concentric 1 093 0 875 knockout for power supply...

Страница 7: ...er of the plenum heater for more information NOTE Some models are not available in two stage at the pre sent time see Electrical Tables The Y2 signal is not used for these units INDOOR LOOP CIRCULATOR...

Страница 8: ...ures equalize in the unit The unit may restart after the timer period has expired Should the unit trip on the safety con trol again the compressor will once again shut down and the counter will be inc...

Страница 9: ...25 MAY 2009 Page 9 000744MAN 02...

Страница 10: ...Page 10 000744MAN 02 25 MAY 2009...

Страница 11: ...7 As the transition from summer to fall begins and the cool ing load is greatly reduced the loops begin to cool down on their own Eventually a point is reached at which the loops are cooled down enou...

Страница 12: ...he COP must be unlocked by command U before using command C to change system settings The list of settings for command C is shown in TABLE 11 It is recommended that the settings be left at the default...

Страница 13: ...25 MAY 2009 Page 13 000744MAN 02...

Страница 14: ...EAT PUMP SIZING TABLE 12 depicts averages WILL VARY WITH ENVELOP EFFICIENCY as a rough guideline to the size of home each heat pump size can handle THE TABLE ABOVE IS FOR INFORMATION ONLY IT SHOULD NO...

Страница 15: ...pass through it to prevent any hot spots in the heater elements TABLE 14 shows the recommended size plenum heater as well as the wire size and breaker size needed to provide power to the plenum heate...

Страница 16: ...Page 16 000744MAN 02 25 MAY 2009...

Страница 17: ...6 15 x 15 20 684 201 1750 18 8 x 40 10 x 30 12 x 24 14 x 20 16 x 17 16 5 x 16 5 20 826 254 2000 18 8 x 40 10 x 30 12 x 24 14 x 20 16 x 17 16 5 x 16 5 22 944 254 2250 20 10 x 38 12 x 30 14 x 26 16 x 22...

Страница 18: ...Page 18 000744MAN 02 25 MAY 2009...

Страница 19: ...25 MAY 2009 Page 19 000744MAN 02...

Страница 20: ...Page 20 000744MAN 02 25 MAY 2009...

Страница 21: ...ine set tubing The line sets can be connected to the ports on the heat pump using couplings or alternately the tubing can be swaged The joints should be silver soldered with 5 silfos AMERICAN DREAM Ge...

Страница 22: ...Page 22 000744MAN 02 25 MAY 2009...

Страница 23: ...ation Record the type of antifreeze and the mixture value on the startup sheet circle Vol or Weight 4 Record the static loop pressure on the startup sheet Line Sets Inside structure 1 Verify that all...

Страница 24: ...l box and compressor 4 Adjust the thermostat setpoint to the desired room temperature and let the unit run through a cycle Record the setpoint and the discharge pressure when the unit shuts off 5 For...

Страница 25: ...connections are correct and securely fastened Circuit breaker or fuse size and wire gauge for Heat Pump A Ga Circuit breaker or fuse size wire gauge and Plenum Heater size A Ga kW Low voltage connect...

Страница 26: ...oop Out Hot Out temperature 7 Indoor Delta T should be between 8 12 F 4 6 C 8 Compressor L1 C current black wire place meter between electrical box and compressor 4 Adjust the aquastat setpoint to the...

Страница 27: ...aker or fuse size wire gauge and Plenum Heater size A Ga kW Low voltage connections are correct and securely fastened Unit Charge Refrigerant charge be fore power is turned on Lbs kg STARTUP DATA Prep...

Страница 28: ...ction at the top of the adjustment record sheet Circle F or C at the top right 2 Record all data for the initial readings elapsed time 0 Adjust the TXV for the loop that is the furthest out Record the...

Страница 29: ...lation Site City Province Country Serial Installer Company Date Model F C TIME COMMON LOOP 1 LOOP 2 LOOP 3 LOOP 4 LOOP 5 LOOP 6 ADJUSTMENT Actual EL S ET D P1 V1 S1 P2 V2 S2 P3 V3 S3 P4 V4 S4 P5 V5 S5...

Страница 30: ...lter 6 months Inspect for dirt Replace if necessary Contactor 1 year Inspect for pitted or burned points Replace if necessary Condensate Drain 1 year Inspect for clogs Remove and clean if necessary Ci...

Страница 31: ...roceed to POWER SUPPLY TROUBLESHOOTING otherwise proceed to STEP 2 STEP 2 Remove the door and electrical box cover and check to see if the HI or LOW LED s are flashing or on Record The results Turn th...

Страница 32: ...AC signal present across C and Stage 1 of the thermo stat Correct the setup Faulty thermostat to heat pump wiring 24VAC signal present across Stage 1 and C of the thermostat but not pre sent across Y1...

Страница 33: ...infinite resistance between any two terminals Note Be sure compressor overload has had a chance to reset If compressor is hot this may take several hours Replace the compressor Burned out motor shorte...

Страница 34: ...Pressure Heating TXV s adjusted too far closed Verify superheat It should be be tween 8 14 F 3 8 C Superheat will be high if TXV is closed too far Adjust TXV to obtain 8 14 F 3 8 C superheat Low Sucti...

Страница 35: ...e or more heating TXV s stuck too far open Adjusting the TXV does not affect the superheat of the loop or the suc tion pressure Low super heat low discharge pressure Adjust the TXV all the way in and...

Страница 36: ...g S and S does not cause the Loop Switch LED to come on or does not cause a loop change Replace the control board High Pressure control and man ual high pressure control trips very fast Faulty reclaim...

Страница 37: ...ir flow are good but suction is low Check static refrigeration pressure of unit for very low value Locate the leak and repair it Spray nine a sniffer and dye are common methods of locating a leak Leak...

Страница 38: ...en White pin 3 and the following at the fan con trol signal harness insert probes in connector where wire is inserted do not unplug the connector Circulation Grey pin 15 Stage 1 Yellow pin 6 Stage 2 Y...

Страница 39: ...at to DXTF Control Box wiring 24VAC not present across Stage 1 C and COM of the aquastat Correct or replace wiring Faulty aquastat to DXTF Control Box wiring 24VAC signal present across Stage 1 NO and...

Страница 40: ...he discharge pressure reduces Surging Discharge Pressure Heating TXV s adjusted too far closed Verify superheat It should be be tween 8 14 F 3 8 C Superheat will be high if TXV s are closed too far Ad...

Страница 41: ...F 3 8 C superheat One or more heating TXV s stuck too far open Adjusting the TXV does not affect the superheat of the loop or the suc tion pressure Low super heat low discharge pressure Attempt to adj...

Страница 42: ...anual Faulty thermostat Thermostat doesn t indicate a call for auxiliary or emergency when it should Replace thermostat Faulty thermostat Thermostat indicates auxiliary or emergency but no 24VAC signa...

Страница 43: ...spect the pump to see if shaft is turning Use an amprobe to measure current draw Replace if faulty Insufficient hot water Heat Pump Prob lem Blockage or restriction in the water line or hot water heat...

Страница 44: ...gerant circuit pressure and connect the vacuum pump to the charging manifold Start the vacuum pump and open the charging manifold valves Vacuum until the vacuum gauge remains at less than 500 microns...

Страница 45: ...25 MAY 2009 Page 45 000744MAN 02 REFRIGERATION CIRCUIT DIAGRAMS...

Страница 46: ...Page 46 000744MAN 02 25 MAY 2009 REFRIGERATION CIRCUIT DIAGRAMS continued...

Страница 47: ...25 MAY 2009 Page 47 000744MAN 02 REFRIGERATION CIRCUIT DIAGRAMS continued...

Страница 48: ...0 802 3 375 43 500 12 7 3 78 65 5 Stage 1 1700 802 2 930 41 900 12 3 4 19 Stage 2 2100 991 4 180 53 300 15 6 3 74 Table 19 Standard Capacity Ratings Cooling 60Hz EAT 80 F 26 7 C STAGE 1 LIQUID LINE 68...

Страница 49: ...g Mode Source Data Indoor Loop Power Consumption Sink Data Outdoor Loop Suct Pres Evap Temp EAT Air Flow LAT Delta T Latent Sensible HAB Compressor Fan Total Electrical Efficiency Disch Pres Cond Temp...

Страница 50: ...0 Hz Cooling Mode Source Data Indoor Loop Power Consumption Sink Data Outdoor Loop Suct Pres Evap Temp EAT Air Flow LAT Delta T Latent Sensible HAB Compressor Fan Total Electrical Efficiency Disch Pre...

Страница 51: ...Hz Cooling Mode Source Data Indoor Loop Power Consumption Sink Data Outdoor Loop Suct Pres Evap Temp EAT Air Flow LAT Delta T Latent Sensible HAB Compressor Fan Total Electrical Efficiency Disch Pres...

Страница 52: ...58 3 5 16 9 20 0 30 10 4 55 15 0 88 4 0 20 0 23 8 40 8 4 65 19 6 123 5 5 26 1 31 0 50 8 4 Models are single stage Table 23 Heat Pump Electrical Information 220 1 50 Model Compressor Fan FLA MCA Max F...

Страница 53: ...25 MAY 2009 Page 53 000744MAN 02 ELECTRICAL DIAGRAMS 230 1 60...

Страница 54: ...Page 54 000744MAN 02 25 MAY 2009 ELECTRICAL DIAGRAMS 230 1 60 continued...

Страница 55: ...25 MAY 2009 Page 55 000744MAN 02 CASE DETAILS Front View Back View Left Side View Right Side View...

Страница 56: ...Page 56 000744MAN 02 25 MAY 2009 Top View Size 2 3 4 Ton CASE DETAILS continued Top View Size 5 Ton...

Страница 57: ...H STAGE 2 STAGE 1 FAN ONLY Recirculation Model Nom Size Full Reduced Full Reduced Full Reduced Tons CFM L s CFM L s CFM L s CFM L s CFM L s CFM L s 25 2 848 400 721 340 721 340 613 289 475 224 404 191...

Страница 58: ...Page 58 000744MAN 02 25 MAY 2009...

Страница 59: ...25 MAY 2009 Page 59 000744MAN 02...

Страница 60: ...only to the completely finished and insulated structure Startup of the unit shall not be scheduled prior to completion of construction and final duct installation for validation of this warranty 4 It...

Отзывы: