3.2
ACR120HE12
ACR180HE18
General Data
Maximum height
M
4.0
Heat medium
Electric heated
Total heat
kW
12
18
Heat setting
2
Heat setting
kW
6 / 12
9 / 18
Fan type
Crossflow
Fan dia
mm
150
Fan settings
2
Air outlet
Fixed
Switching type
Remote switchbox / SmartElec
Weight
kg
38.0
55.0
Electrical Data
Maximum heat capacity
kW
12
18
Supply voltage
415V 3ph 50Hz
Total load
A
29.5
38.4
Starting Current
Low speed amps
A/pha
26.8
34.6
High speed amps
A/pha
29.5
38.4
Running current
Low speed amps
A/pha
25.6
34.5
High speed amps
A/pha
26.6
25.4
Total load
W
29.5
38.4
Cable size
4 x 6.0mm² +Earth (MAX)
External fuse size amps
A/pha
29.5
38.4
Motor power
W
190
** Switch box
pt.
no.
ASCP1-4
Switch box wiring
6 x 1.0mm² + Earth
Mains terminal block position
Top middle - terminals N; L1; L2 & L3
Control terminal block position
Top middle – terminals 1 - 5
** SmartElec Energy Saving Control
pt.
no.
102609
SmartElec Energy Saving Control wiring
2 x pair Belden 8132 (or similar)
Mains terminal block position
SmartElec Base Unit - terminals N; L1; L2 & L3
Control terminal block position
SmartElec Base Unit - terminals A; B; 0V & 7V
Air Data
Fan setting
2
Air volume
Low speed
m³/h
2400
4100
High speed
m³/h
3300
5000
Air velocity
Low @ 0M
m/s
8.5
High @ 0M
m/s
11.0
High @ 1M
m/s
5.5
5.2
High @ 2M
m/s
3.7
3.6
High @ 3M
m/s
2.5
2.4
High @ 4M
m/s
1.6
1.4
Delta T
Low speed
°C
29
27
High speed
°C
23
20
Noise level @ 1M
Low speed
dBA
55
High speed
dBA
60
Dims Data
Length
mm
1150
1750
Depth (width)
mm
550
Total height*
mm
227
Outlet length
mm
1090
1690
Outlet depth (width)
mm
85
Grille height
mm
6
Mounting bracket centres length
mm
1185
1785
Side to 1
st
bracket centre
mm
17.5
Mounting bracket centres height
mm
Flush with top of unit
Top to 1
st
bracket centre
mm
Flush with top of unit
Содержание AIRBLOC ACR Series