19
Overheat
Elements
AC
1
-T
3
THERMAL
GND
GND
GND
GND
SENSOR
DOOR
BMS
Fan Motor
DATA
GND
+12V
L3
AC
2
-T
3
AC
1
-T
2
L2
AC
2
-T
2
AC
1
-T
1
L1
AC
2
-T
1
F1
F2
F3
N
N
AC1
T1
415V 50Hz
Mains Supply
L1
T2
L2
T3
L3
A2
A1
Elements
AC2
T1
L1
T2
L2
T3
L3
A2
A1
4.6 Factory Wiring - Electrically heated 18 & 24kW ONLY
The element outputs are connected to contactors "AC1”
and “AC2” on terminals T1, T2 and T3.
The fan output is connected to a 4 way connector
marked "N”, “F1”, “F2” and “F3".
The thermal trip is connected to a 2 way connector
marked "THERMAL" & “GND”
Terminal
Description
AC1/2-T1
Heater Elements phase 1
AC1/2-T2
Heater Elements phase 2
AC1/2-T3
Heater Elements phase 3
THERMAL
Thermal Overheat trip
GND 0v
Terminal
N
Neutral to fan
F1
Fan - low speed
F2
Fan - medium speed
F3
Fan - high speed
THERMAL
Thermal Overheat trip
GND 0v