13
3.8
SmartElec Controller
General Data
Sensor input
NTC
Control Setpoint
16 to 35 ºC in steps of 1 degree
Temperature Control
Proportional with 1ºC hysteresis
Minimum Power
30% to 99 %
Cycle time
0.3 seconds fixed
Protection
2 x high speed fuse for the protection of the heater switching devices
Fan Output
3 off Relay for High, Medium and Low Fan setting 3A max 240Vac
Connection
Screw terminals 4 for supply, 3 for heater output, 4 for fan output, 2 for
sensor input, 2 for external thermal trip
Supply
415 Vrms +/-15% 50/60Hz 5VA max.
Dimensions
Program panel 101mm(L) x 101mm(W) x 60mm(D) max.
Mounting positions
Program panel fixing centres 80mm x 80mm
Temperature
0 to 50 ºC operating; -20 to 65 ºC storage
Display
Three 7-segment LCD red for parameter display
Push buttons
3 positive feedback tactile push buttons
3.7
Electronic Controller
General Data
Sensor input
NTC
Control Setpoint
16 to 35 ºC in steps of 1 degree
Temperature Control
Proportional with 1ºC hysteresis
Minimum Power
30% to 99 %
Cycle time
0.3 seconds fixed
Protection
2 x high speed fuse for the protection of the heater switching devices
Fan Output
3 off Relay for High, Medium and Low Fan setting
3A max 240Vac
Connection
Screw terminals 4 for supply, 3 for heater output, 4 for fan output, 2 for
sensor input, 2 for external thermal trip
Supply
415 Vrms +/-15% 50/60Hz 5VA max.
Dimensions
Program panel 88mm(L) x 88mm(W) max.
Mounting positions
Program panel fixing centres 60.3mm
Temperature
0 to 50 ºC operating; -20 to 65 ºC storage
Display
Three 7-segment LCD red for parameter display
Push buttons
3 positive feedback tactile push buttons