1.1 Introduction 

This instruction manual describes the Airbloc ACR 
Recessed range of air curtains.  

Models range from 1000mm to 2000mm in length, 
in both Standard and High capacity and are   
available in either Electrically heated, Ambient or 
LPHW. They are designed for discreet positioning 
in a suspended ceiling or bulkhead in the 

 

 

 

 

 

 

doorways  of  retail  or  commercial  premises.      
Optional case for doorways with restricted space 
and no suspended ceiling or bulkhead 

Each air curtain is supplied with a fully electronic 
controller giving multi fan and heat settings 
(electrically operated units) via a simple key pad 
which can be mounted up to 50m from the air  
curtain. Optional BMS time control, external 

 

 

 

thermostats and door interlocks can be installed. 

The program panel shown above allows the user 
to control either a single air curtain, or a network 
of up to 6 air curtains, and provides the following 
functions:- 

- Heat On Off or Auto via optional thermostat 
- Off or Low, Medium and High Fan Speeds 
For further details please refer to section 10.2 

Alternatively on electrically heated models, an  
optional SmartElec control system consists of a 
base unit (installed within the air  curtain) and a 
program panel that can be installed remote from 
the air curtain. Usually, the program panel is 
mounted at a low level from the air curtain for user 
access and to a maximum distance of 50m. The 
base unit and program panel are linked by low 
voltage cable as specified in these instructions.  
 
The SmartElec factory fitted base unit shown 
above provides terminals for 3 phase supply 

 

 

 

connection and the low voltage program panel 
wires. The SmartElec base unit rapidly pulses  
energy to the heating  elements. This combined 
with the inbuilt intelligent sensor control, maintains 
a fixed outlet temperature, thereby reducing 

 

 

 

 

energy consumption as compared to an air curtain 
without the SmartElec control.  

 The program panel shown above allows the user 
to control either a single air curtain, or a network 
of up to 16 air curtains, & provides the following 
functions: 
 

• 

Heat On or Off 

• 

Off  or Low, Medium and High Fan Speeds 

• 

Air Outlet Temperature 

 
For further details please refer to section 10.3 

 
1.2 General

 

All installations must be in accordance with the 
regulations in force in the country of use. 

These instructions must be handed to the user on 
completion of the installation. 

Installers and service engineers must be able to 
demonstrate competence and be suitably qualified 
in accordance with the regulations in force in the 
country of use. 

To ensure continued and safe operation it is     
recommended that the appliance is serviced 

 

 

 

annually. 

The manufacturer, offers a maintenance service. 
Details are available on request. 

The air curtain outlet grille and case air inlet slots 
must not be obstructed during use. 

 

1.3 Electrical 

Supply. 

 
For full electrical loadings, please refer to the   
individual technical data sheets within this manual. 

 

It is recommended that the electrical supply to the 
base unit in the air curtain is via an appropriate 
switched isolator in accordance with the         reg-
ulations in force in the country of use and must be 
via a fused isolator having a contact separation of 
greater than 3mm in all poles. 

General Information 

fig.1. xxxxxxxx Program panel 

fig.2. SmartElec Controller 

Содержание AIRBLOC ACR Series

Страница 1: ...MUST comply with the current IEE wiring regulations 3 Warning this appliance must be earthed INDEX Section General information 1 Dimensions 2 Technical Specification 3 Wiring Details 4 Installation D...

Страница 2: ...4 6 Factory Wiring Electrically Heated 18 24kW 4 7 Factory Wiring Ambient 4 8 Factory Wiring LPHW 4 9 Network Wiring Electronic Controller 4 10 Installer Wiring SmartElec Controller 4 11 Factory Wirin...

Страница 3: ...s terminals for 3 phase supply connection and the low voltage program panel wires The SmartElec base unit rapidly pulses energy to the heating elements This combined with the inbuilt intelligent senso...

Страница 4: ...ilding within the ceiling void or roof space Care must be taken to allow complete free air movement into the inlet grilles of the unit to ensure correct working operation of the air curtain The discha...

Страница 5: ...6 9 ACR100SW9 ACR100SA ACR150SE12 ACR150SW12 ACR150SA ACR200SE18 ACR200SW18 ACR200SA ACR120HE12 ACR120HW12 ACR120HA ACR180HE18 ACR180HW18 ACR180HA A 253 407 B 1220 1520 2020 1185 1785 C 1182 1482 1982...

Страница 6: ...Earthing point Cable Entry 2 3 Optional SmartElec Controller dimensions Cable Entries 13 35 43 5 87 0 60 3crs Cable Entries 7 35 60 3crs 7 35 60 3crs Earthing point 75 0 2 2 Electronic Controller SEL...

Страница 7: ...p middle terminals N L1 L2 L3 Control terminal block position Top middle terminals 1 5 SmartElec Energy Saving Control pt no 102609 SmartElec Energy Saving Control wiring 2 x pair Belden 8132 or simil...

Страница 8: ...N L1 L2 L3 Control terminal block position Top middle terminals 1 5 SmartElec Energy Saving Control pt no 102609 SmartElec Energy Saving Control wiring 2 x pair Belden 8132 or similar Mains terminal b...

Страница 9: ...k position Top middle terminals N L E Control terminal block position Top middle terminals 1 2 Air Data Fan setting 2 Air volume Low speed m h 1164 1475 2013 High speed m h 1646 2085 2851 Air velocity...

Страница 10: ...wiring 4 x 0 75mm Earth Mains terminal block position Front right of centre terminals L N E Control terminal block position Front right of centre terminals 1 2 Air Data Fan setting 2 Air volume Low sp...

Страница 11: ...E Control terminal block position Front right of centre terminals 1 2 Air Data Fan setting 2 Air volume Low speed m h 1164 1475 2013 High speed m h 1646 2085 2851 Air velocity Low 0M m s 4 3 5 4 High...

Страница 12: ...t of centre terminals L N E Control terminal block position Front right of centre terminals 1 2 Air Data Fan setting 2 Air volume Low speed m h 2400 4100 High speed m h 3300 5000 Air velocity Low 0M m...

Страница 13: ...Display Three 7 segment LCD red for parameter display Push buttons 3 positive feedback tactile push buttons 3 7 Electronic Controller General Data Sensor input NTC Control Setpoint 16 to 35 C in step...

Страница 14: ...option Internal External Sensor GND s option 0v terminals 4 1 Installer Wiring Electrically Heated 9 12kW ONLY The program panel is connected to the base unit via a set of 3 way connectors marked 12V...

Страница 15: ...h SENSOR option Internal External Sensor GND s option 0v terminals 4 2 Installer Wiring Electrically Heated 18 24kW ONLY The program panel is connected to the base unit via a set of 3 way connectors m...

Страница 16: ...tch GND s option 0v terminals 4 3 Installer Wiring Ambient The program panel is connected to the base unit via a set of 3 way connectors marked 12V DATA and GND Interconnecting wiring is via Belden ca...

Страница 17: ...tion Internal External Sensor GND option 0v terminals 4 4 Installer Wiring LPHW The program panel is connected to the base unit via a set of 3 way connectors marked 12V DATA and GND Interconnecting wi...

Страница 18: ...2 AC2 T2 AC1 T3 and AC2 T3 The fan output is connected to a 4 way connector marked N F1 F2 and F3 The thermal trip is connected to a 2 way connector marked THERMAL GND Terminal Description AC1 2 T1 He...

Страница 19: ...outputs are connected to contactors AC1 and AC2 on terminals T1 T2 and T3 The fan output is connected to a 4 way connector marked N F1 F2 and F3 The thermal trip is connected to a 2 way connector mar...

Страница 20: ...DATA GND 12V L3 AC2 T3 AC1 T2 L2 AC2 T2 AC1 T1 L1 AC2 T1 F1 F2 F3 N N The fan output is connected to a 4 way connector marked N F1 F2 and F3 Terminal Description N Neutral to fan F1 Fan low speed F2 F...

Страница 21: ...L1 AC2 T1 F1 F2 F3 N N The fan output is connected to a 4 way connector marked N F1 F2 and F3 The thermal trip is connected to a 2 way connector marked THERMAL GND 4 8 Factory Wiring LPHW Terminal De...

Страница 22: ...only to the data cable wiring of 2 or more networked air curtains maximum 6 air curtains per control panel For mains wiring refer to section 4 of this manual installer wiring details The program pane...

Страница 23: ...pply 6mm max L2 Y 3 phase supply 6mm max L3 B 3 phase supply 6mm max Interconnecting Wiring The program panel is connected to the base unit via a set of 4 way re movable connectors marked 7V 0V B and...

Страница 24: ...ermal trip volt free contact is connected to a 2 way connector marked Trip The connection is not polarity sensitive After removing link J1 the BMS pair can be used for external time control via a pair...

Страница 25: ...inals AIR 7V 0V B A Trip BASE UNIT located in air curtain 1 AIR 7V 0V B A Trip BASE UNIT located in air curtain 2 BMS BMS BMS 4 core screened cable suitable cable Belden 8132 2 x twisted pairs Screw t...

Страница 26: ...l heat position depending on their model and capacity size The appliance shall be connected to the supply via an appropriate switched fused double pole isolator having a contact separation of greater...

Страница 27: ...e of the air curtain The brackets may be removed to assist in passing the air curtain through the recess then reattached when in situ Step 6 Either drop rods or catenary wire available from manufactur...

Страница 28: ...he base unit and the program panel can be up to 50m maximum 5 5 Installation details Option SmartElec Controller The SmartElec base unit is pre installed inside the air curtain All the external electr...

Страница 29: ...program panel interconnecting wiring to the 5 6 Installation details LPHW Only With the grille open the heating coils are mounted as shown below The coils can be handed for right or left hand exit by...

Страница 30: ...gle drop of light oil should be applied to the motor bearing from time to time The product should be serviced annually Servicing shall be undertaken by a competent person Airbloc offer a service facil...

Страница 31: ...x xxxxxx Base unit xxxxxx xxxxxx xxxxxx Program Panel Rating 6kW 9kW 12kW 18kW HE Part No 100526 100527 Length 1 0m 1 5m SE Part No 101565 100004 100008 100013 Length 1 0m 1 0m 1 5m 2 0m Element assem...

Страница 32: ...to the nature of it s construction it is not advisable to repair damaged electronic components on either the SmartElec base unit or Program panel ACR200SE18 ACR200SW18 ACR150SE12 ACR150SW12 ACR100SE9...

Страница 33: ...e the temperature to go high and trigger over temperature alarm 1 Polarity Use a multimeter to check correct polarity between all three cores i e that 12V goes to 12V DATA goes to DATA and GND to GND...

Страница 34: ...circuit Heatsink wiring disconnected Check wires Heatsink Broken Replace SmartElec Base unit 10 4 2 SmartElec base unit LED indicator location function No heat fan on or off Heat on fan on Up to temp...

Страница 35: ...g screws by inserting a screwdriver through the hole indicated below Step 4 Lift out element cartridge replace as required 9 1 2 Electrical element replacement HE Step 1 Using a pozidrive screwdriver...

Страница 36: ...towards outside of case Step 4 Disengage rotor bearing Step 5 Disconnect rotor from motor shaft Step 6 Ensure on replacement of rotor that the flat on the rotor bearing aligns with the flat on the mot...

Страница 37: ...t remove Repeat for opposite rotor Step 5 Disconnect the wires from the motor to the mains terminal rail Step 6 Remove the bolts securing the motor to the chassis Replace motor in reverse order Carefu...

Страница 38: ...otes the FAN SPEED This can be either 1 slow 2 medium or 3 fast speed 0 setting denotes the unit is OFF To alter the current speed press the button The value will start flashing Press the or buttons t...

Страница 39: ...rn to the original display The next parameter will either turn the unit On or Off To turn the unit Off press the button On will start flashing Press the button Off will start flashing Press the button...

Страница 40: ...n conjunction with a door switch To access the engineers setting first ensure that the display is in the F FAN parameter Press and hold the b button for 5 seconds Setting d will appear The air curtain...

Страница 41: ...Pressing the button again will advance the display to the outlet SET temperature default S 25 This is denoted by the prefix S followed by the required set temperature in C Temperature settings between...

Страница 42: ...denoted by the prefix F followed by either a 0 for FAN UNIT OFF 1 for LOW FAN 2 for MEDIUM FAN or 3 for HIGH FAN default F 2 Use the or buttons to increase decrease the desired setting DIL SWITCH Eac...

Страница 43: ...43 Notes...

Страница 44: ...ed Kingdom Telephone 01384 489700 Facsimile 01384 489707 Email marketing airbloc co uk Website www airbloc co uk Technical Support www s i d co uk Airbloc is a registered trademark of AmbiRad Limited...

Отзывы: