42
Pressing the button again will return to the first
screen or will return automatically to the first screen
after a period of 3 minutes.
*
‘U 0’
denotes air curtain No.1,
‘U 1’
denotes air
curtain No.2, & so on, up to a maximum of 15.
See
section 4 ‘installer wiring details’ for addressing
instructions.
Pressing the button again will advance the
display to the FAN setting (default =
‘F’ 1
).
This is denoted by the prefix
‘F’
followed by either a
’0’
for FAN (UNIT) OFF,
‘1’
for LOW FAN, ’2’ for
MEDIUM FAN or ’3’ for HIGH FAN (default =
‘F 2’
).
Use the or buttons to increase/decrease
the desired setting.
DIL SWITCH
Each air curtain in the network must have a unique address (0-15) This is achieved using the 4 way
DIL switch mounted on the base unit PCB (see photo).
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
fig. 13. Air curtain address numbers.
10.3.3 SmartElec air curtain addressing
1 2 3 4
ON
OFF
The black shaded areas represent the switch position.
The example opposite shows the air curtain set to No.1.