CHAPTER 3: USING STA SERIES CONTROL FUNCTIONS
STA SERIES AC CONTROLS
990-351
3-13
Section VIII: System Values Screens
System Values Screen 1
To get this screen, go to the
MODE
screen,
highlight
System Values Screen 1
,
and press
the
DATA +
button on the Control Panel.
NOTE:
Some values are detected and displayed
by the Control. They can not be changed by the
operator.
SYSTEM VALUES SCREEN 1
FULL
CURR=10KA
COIL=01X
MAX # OF SCR=1
CO/-
TURNS
RATIO=053:
1
NUM
VALVES=04
CNTRL MODE=%HEAT SEC.
VALVES STATUS
BIN. SCHED. SELECT=OFF MODE=SPOT
FIRING SWITCH=ONE STAGE
More
FULL CURR.
– The full current (
FULL CURR.)
is programmable from
05 kA
to
80 kA
. For proper
operation, this value must be at the current obtained when the unit is fired with a 180
E
conduction angle
into the secondary circuit that will be used for welding. If the transformer taps are changed, this value
must be adjusted.
MAX # OF SCR
– Denotes the number of SCRs available in the Control. The factory-set default is
4
, so
this must be changed to the appropriate number.
TURNS RATIO
– This adjusts the transformer turns ratio for the constant current, and is programmable
from
001:1
to
200:1
.
CNTRL MODE
– Control Mode (
CNTRL MODE
) allows the operator to set the control mode of operation.
Selections are pre-set by the factory and depend on the type of current sensing coil (if any) installed.
%HEAT SEC –
Percent Heat Secondary
SEC. C.C.
– Secondary Constant Current
OR
%HEAT PRI –
Percent Heat Primary
PRI. C.C.
– Primary Constant Current
By placing the cursor at the first character of the
CNTRL MODE
selection and using the
DATA +/–
pushbutton, the operator can toggle between the modes that are applicable to that machine. %HEAT
works for all machines. SEC. CC requires a secondary current coil. PRI CC requires a primary current
coil. Selecting any one of these modes will automatically turn the other modes off. The Control is
shipped in the
% HEAT
mode as the default.
BIN. SCHED. SELECT
– Binary Schedule Select (
BIN. SCHED. SELECT
) determines whether or not the
binary schedule select input is active. That is, it enables or disables the ability for the Control to be
slaved to a separate Programmable Logic Controller (PLC) or other device with BCD capability. There
are only two options,
OFF
or
ON
; the default is
OFF
. If
OFF
, the binary inputs are ignored and the
Control defaults to that which is presented on the control panel. If
ON
, the binary select input is active
and an external device controls which schedule is used. Linking is disabled if Binary Schedule Select is
ON.
FIRING SWITCH
– Selects either two stage or single stage firing switch.
COIL
–This Control has no option; it is set for
1X
.
C/–
–
By placing the cursor at the first character of this field and using the
DATA +/–
pushbutton, the operator can increase or decrease the contrast of the LCD screen.
Содержание Miyachi Unitek STA-100A
Страница 1: ...990 351 Rev H AC WELDER STA SERIES OPERATION MANUAL...
Страница 18: ...CHAPTER 1 DESCRIPTION STA SERIES AC CONTROLS 1 4 990 351 STA 100A Series Major Components Typical...
Страница 24: ......
Страница 28: ......
Страница 48: ......
Страница 64: ......
Страница 68: ...CHAPTER 5 MAINTENANCE STA SERIES AC CONTROLS 5 4 990 351...
Страница 78: ......
Страница 82: ...APPENDIX A TECHNICAL SPECIFICATIONS STA SERIES AC CONTROLS A 4 990 351 STA 200A AC Control Control...
Страница 86: ...APPENDIX B ELECTRICAL AND DATA CONNECTIONS STA SERIES AC CONTROLS B 4 990 351 Input Output Control Signals...
Страница 90: ......
Страница 96: ...APPENDIX D SYSTEM TIMING STA SERIES AC CONTROLS D 2 990 351 Continuous Seam Weld...
Страница 98: ...APPENDIX D SYSTEM TIMING STA SERIES AC CONTROLS D 4 990 351 Spot Welding...
Страница 102: ......
Страница 104: ......
Страница 108: ......
Страница 112: ......
Страница 140: ......
Страница 144: ......
Страница 154: ...AMADA MIYACHI AMERICA INC 1820 South Myrtle Ave Monrovia CA 91016 U S A TEL 1 626 303 5676 FAX 1 626 358 8048...