Always
O
n UPS Systems
Always
O
n UPS Systems
Single line drawing of UPS System
“NX” Series (Generic)
UPS Imax (A) / NFB (A) Rating
I/P
Vac: 120/208 277/480 347/600
10KVA
45/50
20/20 16/20
20KVA
83/90
36/40 30/30
30KVA
125/125
55/60 45/50
40KVA
160/175
70/70 56/60
50KVA
200/200
90/90 70/70
60KVA
250/250
110/110 90/90
80KVA
330/350
145/150 115/125
100KVA
415/450
180/200 145/150
120KVA
500/500
220/225 175/175
160KVA
660/700 290/300 230/250
When choosing a non-fused breaker (NFB) for
the UPS, always choose the NFB that is closest,
but not below the maximum rated input current.
TO LOAD
PANEL
3PH 4W+G
NX Series
RECT
BATS
INV
S.S
S.S
BYPASS
RES
RECT
NFB–3P
4W+G
N
G