15. STATUS INDICATOR TABLE
Indicators:
1=On, 0=Off, R=Red, G=Green,
x=On or Off
Reserve
Breaker ON
Rectifier
Breaker ON
Inverter ON
Inverter
OFF
IP Breaker
OFF
Fault
Condition
REC
AC
FAIL
1 0 0 0 1
RESERVE
FAIL
0 0 0 0 1
FUSE/TEMP
1 >
0 0 0 0 x
OVERLOAD
0 0 0 0 0 x
HIGH
DC
0 0 0 0 0 x
BAT LOW
1
> 0
0
0
x
BAT LOW STOP
1
> 0
0
0
x
FAULT
0 0 0 0 0 1
INVERTER
ON
0 0 1 0 1
INVERTER
SS
1 1 1 0 1 x
SHORT
CIRCUIT
0 0 0 0 0 x
FUSE/OVER
TEMP
SD
0 0 0 0 0 x
INVERTER
FAIL
SHUTDOWN 0 0 0 0 0 x
BYPASS
ON
SHUTDOWN
0 0 0 0 0 x
HIGH
DC
SHUTDOWN
0 0 0 0 0 x
OVERLOAD
SHUTDOWN
0 0 0 0 0 x
70%
LOAD
0 0 x x x x
110%
LOAD
0 0 0 0 0 x
125%
LOAD
0 0 0 0 0 x
150%
LOAD
0 0 0 0 0 x
RESERVE
AC
FAIL
0 0 0 0 1
RESERVE
FREQ
FAIL
0 0 0 0 1
BATTERY LOW
1
> 0
0
0
x
BATTERY LOW SHUTDOWN
0
0
0
0
x
REC
AC
FAIL
1 0 0 0 1
ROTATION
ERROR
1 0 0 0 1
RECTIFIER
SHUTDOWN
0 0 0 0 0 x
HIGH
DC
0 0 0 0 0 x
BOOST
CHARGE
0 0 0 0 0
BATTERY
TEST
0 0 0 0 0
EMERGENCY
STOP
0 0 0 0 0 x
DATA
LINE
x x x x x x
INVERTER MODULE - R
0
> 1
1
1
1
x **
INVERTER MODULE - S
0
> 1
1
1
1
x **
INVERTER MODULE - T
0
> 1
1
1
1
x **
STATIC SW MODULE - R
R
R
R
G
R
x
STATIC SW MODULE - S
R
R
R
G
R
x
STATIC SW MODULE - T
R
R
R
G
R
x
3A - MAIN CONTROL - INV R
1
0*
0
0
0
x ***
3A - MAIN CONTROL - INV S
1
0*
0
0
0
x ***
3A - MAIN CONTROL - INV T
1
0*
0
0
0
x ***
3A - MAIN CONTROL - OTF
1
> 0
0
0
0
x
C - REC CONT - REC ENABLE
0
1
1
1
0
x
ALL PCBs - POWER STATUS
R + G
R + G
R + G
R + G
R + G
x
* Push OFF Button to reset Alarms
** 0 indicates faulted phase
*** 1 indicates faulted phase