Tri Power X33 Mod HP Manual | Rev 1.20 | © Alpha Technologies GmbH 2013
48
6.4
Starting procedure
1. Insert the battery fuses in the relative isolating switches (F B+ and F B-) and, if applicable, those in the Tri Power X33
Mod HP BATTERY cabinets ;
2. Close the switches (F B+ and F B-) and, if applicable, those in the Tri Power X33 Mod HP BATTERY cabinets (if they
exist;
3. With the unit off, press the ENTER key on the operator panel to gain access to the Service Mode. See the next chap-
ter for more information about the SERVICE MODE and panel operation;
4. Follow this path: UPS Setup -
➝
Output
➝
Inverter Select Single-phase / Two-phase /Three-phase 120° / Two separa-
te phases / Three separate phases depending on the connection. Use the arrow keys to move the selection on the
display, the Enter key to confirm, the ESC key to cancel;
5. Following this path: UPS Setup
➝
Batteries
➝
KB. Choose the right numbers of battery strings connected to the UPS.
Use the arrow keys to move the selection on the display, the Enter key to confirm, the ESC key to cancel;
6. Following this path: UPS Setup
➝
Batteries
➝
Capacity folgen. Choose the right capacity each string of connected
batteries. Use the arrow keys to move the selection on the display, the Enter key to confirm, the ESC key to cancel.
The UPS calculate the total capacity by multiplying the no. of string which each capacity;
7. Press the ON/OFF button on the UPS to switch off the unit. All parameters in SERVICE MODE will be stored at this
time;
8. Close the Mains Switch S1 to power the UPS;
9. Press the ENTER button to switch the UPS on;
10. Wait until the status indicator on the display turns blue;
11. Check that the output voltage and frequency values set correspond to the applied load requirements. If they do not,
enter the necessary values (see next chapter);
12. Close the output switch S2 on the UPS
ATTENTION
Before switch on the UPS the correct output configuration has to be selected (Single-phase/Three-phase 120°/
Three separate phases).
INDICATION
The wiring and the settings of the UPS has to be in accordance together.
WARNHINWEIS
Wrong connections or output configuration settings can cause injury to people or damage to equipment!
6. Configuration and Start-up
ATTENTION
When the unit detects the input voltage it automatically proposes starting a battery charging cycle. Press the ‘ESC’
key to proceed to switching the UPS Tri Power X33 on.
WARNING
Even if the installation process is finished, the UPS is only without voltage, if the input switch S1 and the circuit
breaker upstream is open. Only with this condition there is no voltage on the AC terminal present!
If the UPS has internal batteries it will also be necessary to open at least one box for each set (one set consists of 4 bo-
xes). This cuts the power voltage off to the terminal block generated by the various sets of batteries. This must be done
for all sets.