Tri Power X33 Mod HP Manual | Rev 1.20 | © Alpha Technologies GmbH 2013
34
5. Installation
The connection of a Tri Power X33 Mod HP BATTERY to the UPS Tri Power X33 Mod HP 60kVA must be done according to
the following diagram and the steps listed below:
1. make sure that all the battery fuse carrier isolating switches are open;
2. in each Tri Power X33 Mod HP BATTERY remove the lower front panel;
3. In each Tri Power X33 Mod HP BATTERY remove the terminal block loosening the 2 securing srews;
4. connect the UPS and the additional battery cabinet using the earth cable (yellow-green);
5. use the cables supplied with the Tri Power X33 Mod HP BATTERY to connect the positive and negative terminals of
the UPS Tri Power X33 to those of the Tri Power X33 Mod HP BATTERY
TRI POWER X33 MOD HP
BATTERY
TRI POWER X33 MOD HP
BATTERY
TRI POWER X33 MOD HP
40/45/60