0913000-J0 Rev D
38
7.5.2 DC Landing Return and Battery Landing with Top AC Termination Panel
There are a 5 total positions (10 cables back-to-back) to land the battery 'hot' cables when the AC panel is used.
When an AC panel is installed, the left most holes do not go all the way through and only the back 4 are accessible.
See the figure below. The dimensions for holes are 1/2" on 1.75" centers and 3/8" on 1" centers.
There are a total of 4 positions (8 cables back-to-back) to land the DC return cables. The dimensions for holes are
1/2" on 1.75" centers and 3/8" on 1" centers.
Figure 25 — DC connection with AC panel option
DC landing (RETURN),
start here and continue
towards the front.
DC landing (HOT), start
here and move from the
front to the back.
System Front
Start at the front-most corner and move towards the back as shown in the figure below.
NOTE:
While landing the DC return cables, start installing from the rear-most holes and move
your way towards the front as shown in the figure below.
NOTE: