7.5 DC Connections
7.5.1 DC Landing Hot and Battery Landing without Top AC Termination Panel
There are a total of 6 positions (12 cables back-to-back) to land the battery 'hot' cables. The dimensions for the
holes are 1/2" on 1.75" centers and 3/8" on 1" centers.
Start at the front-most corner and move towards the back as shown in Figure 23.
There are a total of 4 positions (8 cables back-to-back) to land the DC return cables. The dimensions for holes are
1/2" on 1.75" centers and 3/8" on 1" centers.
Figure 24 — DC connection without AC panel option
DC landing (HOT), start
here and move from front
to back.
DC landing
(RETURN), start
here and continue
towards the front.
System Front
While landing the DC return cables, start installing from the rear-most holes and move
your way towards the front as shown in the figure below.