3. Specifications
Table A —
Specifications for CXPS-HX 48–2000/2500 Power System
Electrical
AC Input Voltage
No.
of AC
Feeds
Nominal
Voltage
(Vac)
Recommended
Breaker (A)
Connection
Type
Recommended
Wire Size (AWG)
Knockout
Dimension (in)
CXPS-HX-48-2000 (4kW, 4 rectifier shelves) with AC distribution panel
4
208
100
3W + PE
2
2.0 (1.5 KO)
277/480
50
3W + N + PE
6
1.5 (1.25 KO)
8
208
50
3W + PE
6
1.5 (1.25 KO)
277/480
30
3W + N + PE
8
1.5 (1.25 KO)
CXPS-HX-48-2500 (4kW, 5 rectifier shelves) with AC distribution panel
5
208
100
3W + PE
2
2.0 (1.5 KO)
277/480
50
3W + N + PE
6
1.5 (1.25 KO)
10
208
50
3W + PE
6
1.5 (1.25 KO)
277/480
30
3W + N + PE
8
1.5 (1.25 KO)
CXPS-HX-48-2500 (4kW, 5 rectifier shelves) with direct feed to rectifiers and no AC distribution panel
10 (3Ø)
208
50
3W + PE
6
N/A
277/480
30
3W + N + PE
8
N/A
30 (1Ø)
208-277
30
60Hz, (1Ø)
8
N/A
CXPS-HX-48-2000 (12kW/480, 4 rectifier shelves) with AC distribution panel
4
480
50
3W + N + PE
6
1.5 (1.25 KO)
8
480
30
3W + N + PE
8
1.5 (1.25 KO)
CXPS-HX-48-2500 (12kW/480, 5 rectifier shelves) with AC distribution panel
5
480
50
3W + PE
6
1.5 (1.25 KO)
10
480
30
3W + N + PE
8
1.5 (1.25 KO)
CXPS-HX-48-2500 (12kW/480, 5 rectifier shelves) with direct feed to rectifiers and no AC distribution panel
10 (3Ø)
480
30
3W+PE
8
1.5(1.25KO)
Table B — Distribution Panels
Panel Type
Quantity/Rating
Capacity
Max Rating per Panel
TPL Fuses
61 to 800A
Up to 4 positions/ panel
2000A
TPS/TLS
fuses
Up to 125A, 18 per panel
Up to 18 positions/ panel
600A
Bolt-in high
capacity
breakers
1 pole up to 250A
2 pole 275 to 400A
3 pole 450 to 700A
4 pole 650 to 800A
5 pole 850 to 1000A
6 pole 1050 to 1200A
Up to 12 poles/ panel
2000A
Plug-in bullet
breakers
1 pole up to 125A
2 pole 150 to 200A
3 pole 225 to 300A
Up to 18 positions/ panel
600A