29
0913000-J0 Rev D
6.4.3 Temperature Probe for Monitoring Battery Temperature
1. Locate the battery temperature probes coiled up in the power section of the bay.
2. Connect CXC temperature probes from CXC to battery termination post negative.
3. Pick a location at mid-height on one or more battery strings, which will provide a good average temperature
reading; i.e., away from heating or cooling sources.
Figure 18 — Battery temperature probes