9
0913000-J0 Rev D
Table B — Distribution Panels
Panel Type
Quantity/Rating
Capacity
Max Rating per Panel
Output Termination
TPL Fuses
2 hole 1/2" dia. on 1 3/4" centers or
2 hole 3/8" dia. on 1" centers
Allows for dual cable landing back to back
TPS/TLS/AM
breaker
2 hole 1/4" dia. on 5/8" centers
Mechanical
Enclosure
1.095 mm (14 gauge) steel
Mounting
Standard 23" relay rack (flush rack mount) in box bay
Dimensions
H x W x D
Cm: 213H x 71W x 71D
Inches: 84H x 28W x 28D
Environmental
Temperature
0 to + 40°C (32 to 104°F)
Relative humidity
0 to 95% RH non-condensing
Elevation
-500 to 2800 m (-1640 to 9186 ft)
Table C —
Specifications for Related Components
Cordex HP 48-4kW rectifier
See 4kW datasheet on the Alpha website for more detailed information.
Cordex HP 12kW/480, 3P rectifier
See the 12kW datasheet on the Alpha website for more detailed information.
System level alarms/controls
Alarms/control parameters are user-programmable through built-in digital supervisory unit.
See Cordex datasheet for detailed information on alarms and controls.
Indicators
LCD with touch screen
System OK (green LED)
System minor alarm (yellow LED)
System major alarm (red LED)
Load disconnect
-48Vdc, 600A contactor per plug-in bullet panel
-48Vdc, 2000A contactor per TPL fuse or high capacity breaker panel
Alarm connections
0.34 to 2.5 mm
2
(14 to 22AWG)
Smart peripheral modules
Shunt multiplexer
16 shunts per module (up to 2 modules per kit)
Remote hot bar
Mounting
2" Auxiliary framing (customer supplied)
Termination
With 2 kits:
130 sets of 1/2-13 holes on 1-3/4" centers OR
130 sets of 3/8-16 holes on 1" centers
Unit capacity per base kit
5000A per kit
Ultimate capacity
2 kit limit (10,000A)