TECHNICAL DATA TABLE
X31 / X33 - from 10 to 20 kVA
INPUT
Rated voltage [V]
Three-phas (S3T/S3M)
400 (3PH + N)
Single-phase (S3M)
230 (PH + N)
Rated frequency [Hz]
50-60
Accepted tolerance for input voltage [%]
1
± 20 @ 100% load
-40 +20 @50% load
Accepted tolerance for input frequency [Hz]
2
40-72
Technology
IGBT high frequency with PFC control, independent digital
average current mode on each input phase
Input current harmonic distortion [%]
3
THDi
≤
3
Input power factor
≥0.99
Power Walk-in
Programmable from 1 to 120 sec. in steps of 1 sec.
Inrush Current
Imax < In
OUTPUT
Rated voltage [V]
Three-phase (S3T)
380-400-415 (3PH + N)
Single-phase (S3M)
220-230-240 (PH + N)
Rated frequency [Hz]
50/60
Rated apparent output power [kVA]
10
15
20
Rated active output power [kW]
10
15
20
Output power factor
1
Precision of output voltage
(with respect to 400 (230) Vac output voltage) [%]
± 1
Static stability [%]
± 0.5
Dynamic stability
EN62040 -3 Performance Class 1
Output voltage harmonic distortion with standardized
linear and distorting load [%]
< 1% with linear load
≤1.5%
with distorting load
Crest factor allowed at rated load
3:1
Precision of frequency in free running mode [%]
0.01
Inverter overload (Vin>345V AC )
103% Infinite, 110% 60 min, 125% 10 min, 150% 1 min
Bypass Overload
110% Infinite,125% 60 minutes, 150% 10 minutes, 200% 1
min, >200% 2sec
Technology
High frequency IGBT with digital control
BATTERIES
Rated voltage [Vdc]
± 240
Standard maximum recharging current [A]
6
Battery charger algorithm
Two levels with temperature compensation
Technology
Digital controlled PWM regulation
Tolerance of input voltage for recharging at maximum
current [V]
365-480
DIMENSIONS AND WEIGHT
Cabinet type
ACTIVE - ACT
XTEND - XTD
W x D x H [mm]
380 x 850 x 1025
440 x 840 x 1320
Weight without batteries [kg]
(S3T/S3M)
10kVA
72
103
15kVA
74
105
20KVA
76
107
Weight with batteries [kg]
4
(S3T/S3M)
10kVA
278
412
15kVA
280
414
20KVA
282
416
MISCELLANEOUS
10kVA
15kVA
20kVA
Audible noise [dB(A)]
5
S3T/S3M
<40
Color
RAL 7016
Operating ambient temperature
0 – 40 °C
Table 14 – UPS main technical data table