System On direct command
Close the mains input switch (SWIN), the bypass input
switch (SWBYP) if present, and the battery fuse holder
(SWBATT).
Check that the display turns on and the UPS enters into the
"STAND-BY WITH CB OFF" mode.
Verify that the Mains and the Bypass input voltages on the
“System measurements” page are present.
Check that no error messages appear (except “Output Switch open”).
Press the “Menu” icon
and select the “Command
launcher” icon
.
Tap the “SYSTEM ON” command and press OK to confirm.
Wait for a few seconds and check that the UPS turns on
with the output powered by the inverter. The buzzer should
start and the system status should read DISCONNECTED
FROM THE LOAD. This indicates that the output switch
(SWOUT) is not closed and the load is not supplied.
From the
menu select the “bell” icon
if you want to silence the alarm.
Close the Output switch to supply the load and check that
the inverter is correctly powering it.
Verify on the home page that system operating mode is
“ON LINE”.
Check the Output parameters in the Output status page.
Check the battery status (if present) and verify the
measurements.
Set the Date and Time,
Enter the “General and System setting” menu
.
Tap the “Display” icon
and set the desired value in the
Date/Time page.
Store the new settings by pressing the “Save” icon.
In order to return to the main page, press the “HOME” icon.