Default setting for other parameters
In the Table 3 (below) is listed the default setting for other parameters.
FUNCTION
DESCRIPTION
DEFAULT
POSSIBLE
CONFIGURATIONS
Power Walk-In Delay
Delay time of the UPS Power Walk-In
3 sec.
0 - 120 seconds
Power Walk-In
Duration
The duration of the transition mode
Disabled
1 - 120 seconds
Stand-by off Delay
Delay between the mains comeback and the
output UPS switching off
0 sec.
0 - 3600 seconds
Table 3 – Default settings for other parameters (not available from display)
Default configuration of the input/output signals
Output signals configuration (factory default)
Table 4 (below) lists the default configuration of the output signals.
OUTPUT
FUNCTION
DESCRIPTION
OUT 1
Load on Bypass
Load on bypass with closed contact between pin 2 and pin 4;
Otherwise closed contact between pin 1 and pin 4.
OUT 2
Battery working
UPS in battery working with closed contact between pin 3 and pin 4.
OUT 3
Battery low
Battery low with closed contact between pin 8 and pin 6;
Otherwise closed contact between pin 8 and pin 5.
OUT 4
Fault or Lock (F+L)
Fault or lock alarm with closed contact between pin 7 and pin 8.
Table 4 – Default configuration for output signals
Input signals configuration (factory default)
Table 4.1 (below) lists the default configuration of the programmable input signals as provided for factory default
setting.
INPUT
FUNCTION
DESCRIPTION
IN 1
-
-
IN 2
-
-
IN 3
-
-
IN 4
-
-
IN 5
System ON
By externally connecting pin 5 and pin 6 with normally open
contact, when it is closed the UPS switching on.
Table 4.1 – Configuration of input signal in factory default