DISPLAY
Overview
The UPS is equipped with a 5’’ touch screen colour display, through which, amongst others, it is possible to:
view the status of the system;
switch on / switch off the system, activate a battery test and perform bypass operation commands;
configure the system, access levels and the network services.
The “Home” page shows a synoptic diagram of the general operation status of the system. It is possible to interact
with the system and access further information via the icons.
Status Bar
The status bar at the top shows the UPS model, the rated power of the system and the system date and time.
In the event of an alarm an exclamation mark will also be present indicating the number of alarms active at that time.
In parallel system configuration, the status bar shows “-M” if the UPS is master or “-S” if the UPS is slave.
From the top of the status bar the user can access the anomaly/alarm log by pressing the “Exclamation mark” icon.
The “Exclamation mark” icon will only be visible if an anomaly, warning, lock or command occurs.
Icon indicating the existence and number of alarms that are active at that time. If you tap on the icon, a
pop-up will appear showing the individual alarms in detail. To close the pop-up, tap the "exclamation
mark" icon again.
In the list of alarms:
Blue messages indicate warning (W) alarms;
Orange messages indicate anomalies (A) alarms;
Red messages indicate lock (L) alarms and faults (F) alarms.
For the alarm code list, refer to the “STATUS/ALARM CODES” chapter.