External battery temperature probe
An optional temperature probe kit provides the SE UPS with the ability to monitor the temperature within a separate
Battery Cabinet via the terminals located on the power terminal area, identified as “EXT T_BATT” (marked as 3 and
4, refer to the “Power connection details” paragraph of the Installation manual for further information).
This
non-isolated
input can be used also to adjust the battery voltage in accordance with the ambient temperature
(temperature compensation) this feature must be enabled and configured via the configuration software (reserved to
service personnel only).
When the probe is configured, the Ext-Bat value will be shown on the “Sensor status” page.
It is essential that only the kit provided by the manufacturer is used. The use of a temperature probe that
does not comply with the specifications may cause faults or failure of the equipment. Only authorised
personnel can install and activate the temperature probe.
The kit enables the connection of a temperature probe for a Battery Cabinet placed adjacent to the UPS
or up to 10 meters away. If this distance is insufficient then it is possible to extend it up to 25 meters.
To install the External Battery Temperature probe within the Battery Cabinet, refer to the manual provided with the
kit.
Extended run-time
An option is available for an Extended Run-time version (ER) where the maximum charging current can be
increased as follows:
UPS (kVA)
Standard charging current [A]
ER charging current [A]
10
6
12
15- 20
6
20
Table 6 – Extended runtime charging current
This option is available as a factory fitted option.
Dual input
THIS OPTION IS AVAILABLE ONLY FOR THE ACTIVE MODEL. IT IS PROVIDED AS STANDARD ON THE
XTEND MODEL AND IS NOT AVAILABLE ON THE COMPACT MODEL.
THE DI (OPTIONAL) VERSION OF THE UPS SERIES HAS BYPASS INPUT AND MAINS INPUT LINES
SEPARATED.
The UPS series with DI (separate Bypass) ensures a separate connection between the input and bypass lines.
This option is available as a factory fitted option or by purchasing it as a retrofit kit (which can be installed by
authorised service personnel only). In this case, for further details, refer to the Installation manual provided with the