Page
24
to
62
Program
Description
Selectable option
35
Equalization interval
30days (default)
Setting range is from 0 to 90
days. Increment of each click is 1
day
36
Equalization activated
immediately
Enable
Disable (default)
If equalization function is enabled in program 30, this program
can be set up. If “Enable” is selected in this program, it’s to
activate battery equalization immediately and LCD main page
will shows “
”. If “Disable” is selected, it will cancel
equalization function until next activated equalization time
arrives based on program 35 setting. At this time,
“
” will not
be shown in LCD main page.
37
Reset all stored data for
PV generated power and
output load energy
Not reset(Default)
Reset
93
Erase all data log
Not reset(Default)
Reset
94
Data log recorded interval
*The maximum data log
number is 1440. If
it’s over
1440, it will re-write the
first log.
3 minutes
5 minutes
10 minutes (default)
20 minutes