62
4.
PYLONTECH
Lithium Battery Communication Configuration
①
Dip Switch: There are 4 Dip Switches that sets different baud rate and battery group address. If switch position
is turned to the “OFF” position, it means “0”. If switch position is turned to the “ON” position, it means “1”.
Dip 1 is
“ON” to represent the baud rate 9600.
Dip 2, 3 and 4 are reserved for battery group address.
Dip switch 2, 3 and 4 on master battery (first battery) are to set up or change the group address.
Dip switch 2, 3 and 4 on master battery (first battery) are to set up or change the group address.
NOTE:
“1” is upper position and “0” is bottom position.
Dip 1
Dip 2
Dip 3
Dip 4
Group address
1: RS485
baud rate=9600
Restart
to
take
effect
0
0
0
Single group only. It’s required to set up master battery with
this setting and slave batteries are unrestricted.
1
0
0
Multiple group condition.
It’s required to set up master battery
on the first group with this setting and slave batteries are
unrestricted.
0
1
0
Multiple group condition.
It’s required to set up master battery
on the second group with this setting and slave batteries are
unrestricted.
1
1
0
Multiple group condition.
It’s required to set up master battery
on the third group with this setting and slave batteries are
unrestricted.
0
0
1
Multiple group condition.
It’s required to set up master battery
on the fourth group with this setting and slave batteries are
unrestricted.
1
0
1
Multiple group condition.
It’s required to set up master battery
on the fifth group with this setting and slave batteries are
unrestricted.
NOTE:
The maximum groups of lithium battery is 5 and for maximum number for each group, please
check with battery manufacturer.