Section 9 |
Control
Menu 5.1.2 - max flow line temperature
Menu 5.1.4 - alarm actions
Menu 5.1.5 - fan sp. exhaust air
(additional equipment required)
Menu 5.1.3 - max diff flow line temp.
Here you set the start and stop temperature of the hot
water for the different comfort options in menu 2.2 as
well as the stop temperature for periodic increase in
menu 2.9.1.
Set the maximum supply temperature for the climate
system here. If the installation has more than one cli-
mate system, individual maximum supply tempera-
tures can be set for each system. Climate systems 2
- 8 cannot be set to a higher max supply temperature
than climate system 1.
If the current supply temperature exceeds the calcu-
lated flow with set value, the degree minute value
is set to 0. The compressor in the heat pump stops
when there is only a heating demand.
If "addition” is selected and activated in menu 4.2 and
the present supply temp exceeds the calculated with
set value, the additional heat is forced to stop.
Select how you want the control module to alert you
that there is an alarm in the display here. The different
alternatives are; the heat pump stops producing hot
water and/or reduces the room temperature.
Here you set the maximum permitted difference be-
tween the calculated and actual supply temperature dur-
ing compressor respectively add. heat mode. Max diff.
additional heat can never exceed max diff. compressor
stop temp. per. increase
Setting range: 55 – 60°C
Factory setting: 55°C
step difference compressors
Setting range: 0,5 – 4,0 °C
Factory setting: 1,0°C
charge method
Setting range: target temp, delta temp
Factory setting:delta temp
climate system
Setting range: 5-70°C
Factory setting: 55 °C
max diff compressor
Setting range: 1 – 25 °C
Factory setting: 10 °C
max diff addition
Setting range: 1 – 24 °C
Factory setting: 7 °C
max diff addition
max diff compressor
CAUTION
Underfloor heating systems are normally max flow
line temperature set between 35 and 45 °C.
In order to obtain information on the maximum permit-
ted temperature, ask the floor supplier / contractor for
floor heating and the heating system.
CAUTION
If no alarm action is selected, it can result in higher
energy consumption in the event of an alarm.
CAUTION
An incorrectly set ventilation flow can damage the
house and may also increase energy consumption.
Set the speed for the five different selectable speeds
for the fan here.
normal and speed 1-4
Setting range: 0 – 100 %
Factory setting: normal: 75%
Factory setting: speed 1: 0%
Factory setting: peed 2: 30%
Factory setting: speed 3: 80%
Factory setting: speed 4: 100%
IMPORTANT
Menu 5.1.5 is inactive in the factory settings. For this
menu function to be active, the accessory must be in-
stalled and activated in the accessories menu. 5.2.4.
For detailed information on the accessory settings,
refer to the respective accessory's manual.