72
HM 6Split
HM 12Split
Max. operating current and recommended fuse rating
for 3x400 V connection
Unit
HM 6Split
+ L 6Split
HM 12Split
+ L 8Split
HM 12Split
+ L 12Split
Max. operating current,
compressor
A
16
16
20
Max. operating current of heat pump including 3 kW
immersion heater, compressor running and contactor
K1 connected (recommended fuse rating)
A
16 (16)
16 (16)
20 (20)
Max. operating current of heat pump including 6 kW
immersion heater, compressor running and contactor
K1+K2 connected (recommended fuse rating)
A
16 (16)
16 (16)
20 (20)
Max. operating current of heat pump including 9 kW
immersion heater, compressor running and contactor
K1+K2+K3 connected (recommended fuse rating)
A
20 (20)
20 (20)
20 (20)
Max. operating current of 9 kW immersion heater,
contactor K1+K2+K3 connected, compressor not
running (recommended fuse rating)
A
20 (20)
20 (20)
20 (20)
Max. operating current and recommended fuse rating
for 1x230 V connection
Unit
HM 6Split
+ L 6Split
HM 12Split
+ L 8Split
HM 12Split
+ L 12Split
Max. operating current.
compressor
A
16
16
20
Max. operating current of heat pump including 1.5 kW
immersion heater. compressor running and contactor
K1 connected
(recommended fuse rating)
A
22,5 (25)
22,5 (25)
26,5 (25)
Max. operating current of heat pump including 3 kW
immersion heater. compressor running and contactor
K1+K2 connected
(recommended fuse rating)
A
29 (32)
29 (32)
33 (32)
Max. operating current of heat pump including 4.5 kW
immersion heater. compressor running and contactor
K1+K2+K3 connected (recommended fuse rating)
A
35,5 (32)
35,5 (32)
39,5 (40)
Max. operating current of 4.5 kW immersion heater.
contactor K1+K2+K3 connected. compressor not
running
(recommended fuse rating)
A
19,5 (20)
19,5 (20)
19,5 (20)
Section 13 |