44
HM 6Split
HM 12Split
Section 9 |
Control
In this menu we have the option to change settings
for the additional heat (built-in electric additional heat).
More information after selecting "?".
Factory setting:
add.type: step controlled
positioning before QN10 (REQUIRED)
max step: 3
binary stepping: inactive
fuse size: 20 A
transformation ratio: 300
In this menu, it is possible to select slave devices.
More information after selecting "?".
Factory setting:
slave 1: active (EB101)
In this menu it is possible to edit the device operation
scheme. More information after selecting "?".
IMPORTANT
Changing the diagram will cause the device to operate
incorrectly.
8/18 Addition
IMPORTANT
In the case of a lower security (for the main security in
the building), this value can be set lower than 20 A. Cau-
tion, this will cause a decrease in the device's power.
You can not set a value higher than 20A.
The before QN10 setting cannot be changed.
9/18 Installed slaves
Recommended setting values are:
+ 35 for surface heating,
+ 55 for radiator heating.
Detailed information on curve settings - see pt.
"
User
settings".
In this menu, set the current date and time. In addi-
tion, we have the ability to choose the display format
and time zone.
In this menu it is possible to edit the minimum flow
temperature of the heating system. More information
after selecting "?".
Factory setting:
climate system 1: 20 C
In this menu it is possible to edit the maximum flow
temperature of the heating system. More information
after selecting "?".
Factory setting:
climate system 1: 55 C
In this menu it is possible to edit the heating curve
specified for the HM 6Split / HM 12Split unit. More
information after selecting "?".
Factory setting:
Heating curve: 7
CAUTION
The above settings regarding the device operating
schedule can only be edited by qualified personnel.
11/18 Time & date
12/18 Min. flow line temp.
13/18 Max flow line temp.
14/18 Heating curve
10/18 Docking